30
Amended: April 22
EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Input Programming General Rules
Function
Operational
Results
Comments
Fire
Yes
Fire Event on all panels,
local and network
This is the default
programming
Fault
Yes
General fault on all panels,
local and network
Reset
Yes
Performs a Soft reset on all
panels, local and network
Silence
Yes
Silences local and
networked panels
Will also accept
T1/T2
Technical Input
Yes
No indication on display,
creates a log entry affects
local and networked panels
Active from Jul 17
Provides feedback
for FC6 and smoke
management
Evacuate
Yes
Sends an Evacuation
command
– overrides most
programming on local and
network
Fire/Extinguisher
Activate
N/A
German mode only
FRE Activate
N/A
German Mode only
Non-Fire
Yes
No indication on display
creates a log entry Local
Panel Only
Local devices (loop
card) can be
programmed to
respond to this input,
by address (same
loop) or by specified
zone.
Performance Mode
N/A
Cascade
N/A
Custom Trigger
N/A
FPE Feedback
N/A
German Mode only
Isolate Addresses
Yes
No indication on screen
–
will initiate a disablement
Led
– total number of
addresses to isolate from
this address is 8
Non latch function
not required
Isolate Zones
Yes
No indication on screen
–
will initiate a disablement
Led
– total number of zones
to isolate from this address
is 8
Non-Latch function
not required
Does not work with
zone grouping
Non Latch
Yes
When the fire condition is
removed the panel local and
network performs a soft
reset
Used for interlinking
Day Night
Yes
When ticked for Day Night
any other device on the
same Loop controller will
follow this signal. When in
night mode a crescent moon
icon appears adjacent to the
top LH corner screen touch
box, no further indication.
Devices affected by
this function are
Opto-Thermal smoke
and Heat detectors.
Table 2
Summary of Contents for DF6200
Page 1: ...DF6000 Applications Guide Including CF3000 FX6000 CF11 1200 DF61 6200 Annex 1 CF2000...
Page 29: ...29 Amended April 22 EMEA Fire Technical Support DF6000 CF3000 Applications Guide Fig 16...
Page 81: ...81 Amended Sept 21 Fig 73 Fig 74...
Page 84: ...84 Amended Sept 21 Fig 79...
Page 94: ...94 Amended Sept 21 Return to beginning of document End of Document...