63
Amended: April 22
EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
From Jun17 a new device which also replies as a repeater has been introduced to provide
compliance to this regulation.
The BS 7273 interface is programmed in the same format as all previous repeaters. Right click the
device icon and choose ‘Edit repeater’ from the drop box highlight ‘BS7273 interface’.
Fig 60
Two output stages are provided on this device with up to 5 rules each. Each rule, if selected for
BS7273 specific, See Fig 60, will have 3 condition sources, Fire , Fault and Disablement by default.
Trigger sources by Zone, device or global can then be selected. You can build your own rules if
required.
The BS7273 device has a loop in and out connection but is powered from an external 24v PSU.
If the PSU has volt free contacts for Mains and Battery Faults then the BS7273 device has 2 input
terminals with 6K8 EOL capable of monitoring the volt free contacts.
NOTE These Devices can not be used on CF2000
Touch Screen Repeater
The Touch screen repeater is ONLY networkable but allows the user much more control such as
disabling devices across the network. This panel also has a programmable input and Fire and Fault
relays.
Summary of Contents for DF6200
Page 1: ...DF6000 Applications Guide Including CF3000 FX6000 CF11 1200 DF61 6200 Annex 1 CF2000...
Page 29: ...29 Amended April 22 EMEA Fire Technical Support DF6000 CF3000 Applications Guide Fig 16...
Page 81: ...81 Amended Sept 21 Fig 73 Fig 74...
Page 84: ...84 Amended Sept 21 Fig 79...
Page 94: ...94 Amended Sept 21 Return to beginning of document End of Document...