Eaton Cuttler-Hammer Pow-R-Command 100 Instruction Leaflet Download Page 18

Installation Leaflet

Page 18                Effective: April 2003

Pow-R-Command 100

IL01412003

      For More Information visit www.cutler-hammer.com

APPLICATION EXAMPLE 5: DIMMING
APPLICATIONS WITH THE SOC

All the PRC100 Controllers have similar
capabilities for input, output and functions.
The following application will demonstrate
connections for both manual and automatic
dimming of florescent fixtures.

The figure shows the major components
required for manual and automatic dimming
control. These components are shown
attached to the SOC but the same control
can be applied to the USC and other ASC’s.
Certain parameters must be entered into the
system to compensate for the different
characteristics of the devices. For example
the PLC photo sensors have different FC
ranges but all have 1 to 5 Volt signals. The
conversion to percent or units would be
determined at the time of start-up. With the
connections shown here control strategies
such as Lumen Maintenance, Daylight
Harvesting, and manual control as well as
manual control to a variable set point can
be accomplished through programming the
controller database. It is imperative that the
sensor type associated with each input be

provided to the Cutler-Hammer engineer for
proper start-up and operation of the
dimming controls.

PLC MULTIPOINT® SENSOR NOTES.
The CES series of sensors have different
input ranges but are normalized to a 1 to 5
volt output. While these relationships are
adjustable at the sensor it is probably better
to make any adjustment using the control-
lers built-in type definitions. The CES Series
sensors are supplied from the factory with
the following calibrated ranges.

CES®/I

0 to 100 FC = 1 to 5 V

CES/O

0 to 250 FC = 1 to 5 V

CES/A

2 to 1000 FC = 1 to 5 V

CES/S

10 to 2000 FC = 1 to 5 V

The adjustable Maximums for these
sensors are:
CES/I

5 to 750 FC

CES/O

5 to 750 FC

CES/A

200 to 2500 FC

CES/S

1000 to 7500 FC

LEVITON IP710-DLW

The LED provided in this switch is hard-
wired internally as a night-light. This switch
is intended for connection to a 120 V AC
circuit and thus it uses a small amount of
leakage to illuminate the LED when the lights
are off. When using this device with a PRC
controller it is limited to where it can be
connected. Connecting this device to any of
the DIGITAL INPUTS (DI 9, 10, 11, 12) will
cause improper operation of the input due to
this leakage. The Digital Inputs provide
sufficient whetting voltage to cause the LED
to conduct and thus the circuit will never
open. For this reason the Leviton switch will
only function when connected to the
Universal Inputs (Analog Inputs 1 – 8) or
wired to the Control Cabinet, Expansion
Chassis or Relay Panel switch termination
blocks. In either case the LED will not
illuminate and is unusable for this

application.

Figure 4-20: Application Example SOC Switch Inputs

SOC

BLK

RED

WHT

Cutler-Hammer

016-4092

Dimming Cable

Yellow To Lamps

Red    VIO-CV

BLK    GRA - COM

40 Ballasts Max

Red - Power

BLK - COM

YEL - Signal

BLK - AC Supply

WHT

Advance Transformer
MARK VII®

RED To Lamps

BLUE

PLC Multipoint
CES/I-1/5
CES/O-1/5
CES/A-1/5
CES/S-1/5

GRA - COM

VIO - Variable

BLK - Switched

RED - Switch COM

BLK - Switched

Leviton IP710 -DLW

Summary of Contents for Cuttler-Hammer Pow-R-Command 100

Page 1: ...April 2003 Pow R CommandTM PRCTM 100 Instruction Leaflet IL01412003 For More Information visit www cutler hammer com...

Page 2: ...EME CAUTION WHEN OPERATING THE SYSTEM DANGEROUS VOLTAGES MAY EXIST INSIDE THE UNITS Failure to follow any or all warnings and instructions contained herein may cause severe injury or death and or dama...

Page 3: ...CTION 4 APPLICATION SPECIFIC CARD TERMINATION 10 4 1 UNIVERSAL SYSTEM CONTROLLER 10 4 2 SWITCH OVERRIDE CONTROLLER 10 4 3 UNIVERSAL I O MODULE 11 4 4 LOW VOLTAGE INPUTS OUTPUTS 11 4 5 LOW VOLTAGE WIRI...

Page 4: ...GHBS or BABR breakers using the time schedules or the console Panelboard with 5X Controller Chassis and 7X Expansion Chassis see Fig 1 2 2 Combining the 5X Controller Chassis the 7X Expansion Chassis...

Page 5: ...s mounted in the panel For low voltage device termination please refer to SECTION 3 Subsection 3 2 For remote controlled breaker termination please refer to SECTION 3 Subsection 3 3 1 3 RELAY PANEL A...

Page 6: ...sible for providing and terminating the power wires to these panels If the trim is installed remove the trim for the Expansion Control Cabinet remove the door and the power supply cover There are two...

Page 7: ...Power supply and Network connections will be provided in the factory In rare case of the 7X Expansion Chassis located externally to the panel the network cable and the power supply cable should be ins...

Page 8: ...ly described enclosure types to attach conduit and provide access to the low voltage termination area Panels using Expansion Cabinet might or might not contain 5X Controller Chassis For panels with a...

Page 9: ...e connectors are numbered 1 24 on the left side of the board and 25 48 on the right side of the board see Fig 3 3 On the Panel side the pigtails are connected to the low voltage connectors on the back...

Page 10: ...of an Expansion Control Cabinet The SOC will accept only dry contact closure devices i e switches occupancy sensors Building Management System relay etc Contact closure is processed by the SOC card re...

Page 11: ...e 100 mA for powering external devices The 24VAC used to power controllers can also be used for powering external devices Although each controller may differ in the number of low voltage control point...

Page 12: ...onnectors The input can be defined at start up as a variety of maintained and momentary contact configurations One special use for these inputs is a counter function This function can be used for a va...

Page 13: ...itch 24VDC or 24VAC The outputs are defined at start up as normally open or closed and maintained or pulsed The pilot lamp digital outputs on an SOC controller provide a 24VDC half wave rectified sign...

Page 14: ...an be wired adjacent to each other In this case the lower number represents the DOWN lower position or OFF action while the higher number represents the UP or TOP action Figure 4 16 Application Exampl...

Page 15: ...reduce the number of conductors required to pull The SOC has the same inputs as described above for the USC The differences being the connectors are located along the left edge of the controller SPECI...

Page 16: ...the LED Wiring the Pilot s as described in this note would allow for two modes of operation The Pilot could act as feedback showing the resulting state of a remote load In other words when the load is...

Page 17: ...the difference being the location of the connectors The CO2 Sensor shows all modes con nected This sensor could provide direct analog input through the 250 Ohm resistor and can also provide closures...

Page 18: ...bly better to make any adjustment using the control lers built in type definitions The CES Series sensors are supplied from the factory with the following calibrated ranges CES I 0 to 100 FC 1 to 5 V...

Page 19: ...Occupancy sensor would have the load controlling the 120VAC to the light fixtures as its control output The switches control dimming and the sensor controls on off There are many alternatives to this...

Page 20: ...These timers delay keep the lights on for an adjustable period of time AFTER sensing no activity For best results with lighting control systems it is recom mended that this delay be set to minimum an...

Page 21: ...n Loops are not allowed on the network The ends of the Network should be terminated with the End of the Line Resistors A 12 Ohm resistors must be placed on the furthest two panels on the network One e...

Page 22: ...cable S bottom pin on the connector shield of the network cable Network In Terminals Network Out Terminals Figure 5 3 Panelboard 5X Controller Chassis Network Terminations Knockouts Note As mentioned...

Page 23: ...al Connect shield of the cable to the SHLD terminal see Fig 5 4 For the panel in the middle of the network connect the end of the incoming cable to the IN IN and SHLD and the end of the outgoing cable...

Page 24: ...ctly to the RIB board see Fig 5 7 The connectors for the network are provided at the factory Remove the plug from the socket on the RIB board Terminate the network cable in the plug and push it back i...

Page 25: ...ll offer greater protection against this interference This text is intended as a guideline for the use of repeaters it is in no way all inclusive Because of the nature of the PRC100 implementation of...

Page 26: ...ected to the terminal The shield is connected to the third terminal If the NIB is located at the end of the Network a 120 ohm termination resistor should be connected between the and terminals 6 1 NIB...

Page 27: ...ork to a PC using a standard Ethernet connection but also allow for remote access via a phone line In this case the Ethernet Server need not be physically located near the PC but rather near the Ether...

Page 28: ...or one person to perform this by pre addressing all cards at one panel This would require a temporary connection of the NIB to a panel and a PC connected to the NIB Each card is then added to the netw...

Page 29: ...yed right of center at the top of the window beneath the text Step 4 of 5 This time out will count down from 30 seconds and then explain that the RESET button must be pressed before clicking the Finis...

Page 30: ...system table The following steps briefly describe this procedure STEP 1 Connect the network test tool to the four pin test connector on the controller or nearby networked controller STEP 2 Launch the...

Page 31: ...t parameter screen enter the desired address for this controller Remember that controller addresses must be unique DO NOT choose an address already assigned to another controller STEP 12 Tap OK in the...

Page 32: ...ssistance Please Contact Your Cutler Hammer Representative Eaton Corporation Cutler Hammer business unit 1000 Cherrington Parkway Moon Township PA 15108 United States tel 1800 525 2000 www cutler hamm...

Reviews: