IQ DP-4000
APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES
TD 17548B
57
■
= OFF
❑
= ON
CT
Values
Switch Settings
Pressing & Holding S1 causes all 8 switches on S2 to be saved according to the Rotary Switch S3.
Always set all 8 S2 switches. See Figure 2.2 (p.4) and Table 5.A (p.21).
CT
Primary
Rotary
Switch
S3.1
S3.3
(CT:5)
Setpoint
Switch
S2.8
S2.1
S2.2
S2.3
S2.4
S2.5
S2.6
S2.7
S2.8
5
off
off
off
off
off
off
off
off
off
10
off
on
off
off
off
off
off
off
off
15
off
off
on
off
off
off
off
off
off
20
off
on
on
off
off
off
off
off
off
25
off
off
off
on
off
off
off
off
off
30
off
on
off
on
off
off
off
off
off
35
off
off
on
on
off
off
off
off
off
40
off
on
on
on
off
off
off
off
off
45
off
off
off
off
on
off
off
off
off
50
off
on
off
off
on
off
off
off
off
55
off
off
on
off
on
off
off
off
off
60
off
on
on
off
on
off
off
off
off
65
off
off
off
on
on
off
off
off
off
70
off
on
off
on
on
off
off
off
off
75
off
off
on
on
on
off
off
off
off
80
off
on
on
on
on
off
off
off
off
85
off
off
off
off
off
on
off
off
off
90
off
on
off
off
off
on
off
off
off
95
off
off
on
off
off
on
off
off
off
100
off
on
on
off
off
on
off
off
off
105
off
off
off
on
off
on
off
off
off
110
off
on
off
on
off
on
off
off
off
115
off
off
on
on
off
on
off
off
off
120
off
on
on
on
off
on
off
off
off
125
off
off
off
off
on
on
off
off
off
130
off
on
off
off
on
on
off
off
off
135
off
off
on
off
on
on
off
off
off
140
off
on
on
off
on
on
off
off
off
145
off
off
off
on
on
on
off
off
off
150
off
on
off
on
on
on
off
off
off
155
off
off
on
on
on
on
off
off
off
160
off
on
on
on
on
on
off
off
off
165
off
off
off
off
off
off
on
off
off
170
off
on
off
off
off
off
on
off
off
175
off
off
on
off
off
off
on
off
off
180
off
on
on
off
off
off
on
off
off
Summary of Contents for Cutler-Hammer IQ DP-4000