IQ DP-4000
APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES
TD 17548B
64
■
= OFF
❑
= ON
CT
Values
Switch Settings
Pressing & Holding S1 causes all 8 switches on S2 to be saved according to the Rotary Switch S3.
Always set all 8 S2 switches. See Figure 2.2 (p.4) and Table 5.A (p.21).
CT
Primary
Rotary
Switch
S3.1
S3.3
(CT:5)
Setpoint
Switch
S2.8
S2.1
S2.2
S2.3
S2.4
S2.5
S2.6
S2.7
S2.8
*500
on
on
off
off
on
off
off
off
off
*550
on
off
on
off
on
off
off
off
off
*600
on
on
on
off
on
off
off
off
off
*650
on
off
off
on
on
off
off
off
off
*700
on
on
off
on
on
off
off
off
off
*750
on
off
on
on
on
off
off
off
off
*800
on
on
on
on
on
off
off
off
off
*850
on
off
off
off
off
on
off
off
off
*900
on
on
off
off
off
on
off
off
off
*950
on
off
on
off
off
on
off
off
off
*1000
on
on
on
off
off
on
off
off
off
*1050
on
off
off
on
off
on
off
off
off
*1100
on
on
off
on
off
on
off
off
off
*1150
on
off
on
on
off
on
off
off
off
*1200
on
on
on
on
off
on
off
off
off
*1250
on
off
off
off
on
on
off
off
off
1300
on
on
off
off
on
on
off
off
off
1350
on
off
on
off
on
on
off
off
off
1400
on
on
on
off
on
on
off
off
off
1450
on
off
off
on
on
on
off
off
off
1500
on
on
off
on
on
on
off
off
off
1550
on
off
on
on
on
on
off
off
off
1600
on
on
on
on
on
on
off
off
off
1650
on
off
off
off
off
off
on
off
off
1700
on
on
off
off
off
off
on
off
off
1750
on
off
on
off
off
off
on
off
off
1800
on
on
on
off
off
off
on
off
off
1850
on
off
off
on
off
off
on
off
off
1900
on
on
off
on
off
off
on
off
off
1950
on
off
on
on
off
off
on
off
off
2000
on
on
on
on
off
off
on
off
off
2050
on
off
off
off
on
off
on
off
off
2100
on
on
off
off
on
off
on
off
off
2150
on
off
on
off
on
off
on
off
off
2200
on
on
on
off
on
off
on
off
off
2250
on
off
off
on
on
off
on
off
off
2300
on
on
off
on
on
off
on
off
off
* These CT Primary values are repeated from previous pages. Either setting is acceptable