SECTION 5 - PROGRAMMING THE IQ DP-4000
TD 17548B
30
= OFF
= ON
Alarm 1
(Set all 8 S2 switches)
Alarm 2
Reset
Level,
S3.C
S3.C
%
S2.1
S2.2
S2.3
S2.4
S2.5
S2.6
off
off
off
off
off
off
0
on
off
off
on
off
off
10
off
on
off
off
on
off
20
on
on
off
on
on
off
30
off
off
on
off
off
on
40
on
off
on
on
off
on
50
off
on
on
off
on
on
75
on
on
on
on
on
on
100
Table 5.W Reset Threshold Settings
5.12.15.1 Overvoltage Reset Threshold
To determine the threshold level to reset the
overvoltage, find the voltage when an overvoltage alarm
will occur. This is the nominal AC line voltage (see
Section 5.5) multiplied by the overvoltage detection
level (see 5.12.12 p.29). Figure 5.1 (p.31) illustrates the
overvoltage set and reset levels.
The reset voltage is a percentage of the difference (0 to
100%) between the nominal voltage and the
overvoltage detection level, as determined by the reset
threshold. You can calculate this by:
OVR = OVDL - RST x (OVDL - NOM)
where
OVR = Overvoltage Reset (Volts)
RST = Reset Threshold
OVDL = Overvoltage Detection Level (Volts)
NOM = Nominal AC line Voltage (Volts)