IQ DP-4000
APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES
TD 17548B
58
■
= OFF
❑
= ON
CT
Values
Switch Settings
Pressing & Holding S1 causes all 8 switches on S2 to be saved according to the Rotary Switch S3.
Always set all 8 S2 switches. See Figure 2.2 (p.4) and Table 5.A (p.21).
CT
Primary
Rotary
Switch
S3.1
S3.3
(CT:5)
Setpoint
Switch
S2.8
S2.1
S2.2
S2.3
S2.4
S2.5
S2.6
S2.7
S2.8
185
off
off
off
on
off
off
on
off
off
190
off
on
off
on
off
off
on
off
off
195
off
off
on
on
off
off
on
off
off
200
off
on
on
on
off
off
on
off
off
205
off
off
off
off
on
off
on
off
off
210
off
on
off
off
on
off
on
off
off
215
off
off
on
off
on
off
on
off
off
220
off
on
on
off
on
off
on
off
off
225
off
off
off
on
on
off
on
off
off
230
off
on
off
on
on
off
on
off
off
235
off
off
on
on
on
off
on
off
off
240
off
on
on
on
on
off
on
off
off
245
off
off
off
off
off
on
on
off
off
250
off
on
off
off
off
on
on
off
off
255
off
off
on
off
off
on
on
off
off
260
off
on
on
off
off
on
on
off
off
265
off
off
off
on
off
on
on
off
off
270
off
on
off
on
off
on
on
off
off
275
off
off
on
on
off
on
on
off
off
280
off
on
on
on
off
on
on
off
off
285
off
off
off
off
on
on
on
off
off
290
off
on
off
off
on
on
on
off
off
295
off
off
on
off
on
on
on
off
off
300
off
on
on
off
on
on
on
off
off
305
off
off
off
on
on
on
on
off
off
310
off
on
off
on
on
on
on
off
off
315
off
off
on
on
on
on
on
off
off
320
off
on
on
on
on
on
on
off
off
325
off
off
off
off
off
off
off
on
off
330
off
on
off
off
off
off
off
on
off
335
off
off
on
off
off
off
off
on
off
340
off
on
on
off
off
off
off
on
off
345
off
off
off
on
off
off
off
on
off
350
off
on
off
on
off
off
off
on
off
355
off
off
on
on
off
off
off
on
off
360
off
on
on
on
off
off
off
on
off
365
off
off
off
off
on
off
off
on
off
Summary of Contents for Cutler-Hammer IQ DP-4000