IQ DP-4000
SECTION 3 - OPERATOR PANEL
TD 17548B
11
Figure 3.4 Induction Motor Load
Figure 3.5 Power Distribution
Note:
Refer to section 5.11(p.26) VAR/Power Factor
Sign Convention Setpoint for more information
about + and - values.
3.1.3.3 Units LEDs: Auto Range Units for Monitoring
The units for monitoring are Units, Kilo-Units, and
Mega-Units. Figure 3.1 (p.8) shows the location of
these LEDs to the right of the display window. These
units are fixed, based on your selection for PT and CT
ratios so that the display is consistent with the PT and
CT sizes. They let you know the measurement unit for
the displayed function.
3.1.3.4 Alarm LED’s
The Alarm LEDs, (Alarm 1, Alarm 2) when continuously
lit, indicate that an alarm condition exists. If there is an
alarm condition when you press the Alarm Data button,
the corresponding LED blinks and the display window
shows a digit, from 1 to 8. This digit represents the
specific type of alarm condition that is occurring for the
selected alarm. The alarm cause codes are listed at the
bottom of the faceplate for easy reference. Table 3.A
describes the alarm codes by number.
Alarm
Cause Code
Operator Panel
Designation
Description
1
External
Remote
device
initiates
alarm
2
3
4
5
6
7
Overvoltage
Undervoltage
Phase Voltage
Unbalance
Voltage Phase Loss
Current Phase Loss
Phase Reversal
An alarm
condition
occurs
8
Malfunction
Internal Data
Out of
Range
Cycle Power.
Table 3.A Alarm Codes