OPERATION
22
STOPPED BEFORE FUNCTION CODE
VALUES ARE MODIFIED WHENEVER
POSSIBLE.
If an invalid Function Code is specified, the control
ignores the selection and displays the current
count value. An invalid Function Code is any code
not listed in Figure 21.
If an invalid value is entered in a Function Code,
the control may ignore or modify the entry. If
ignored, the previous setting is retained. An invalid
value is any value other than those allowable val-
ues listed in Figure 21.
When shipped from the factory, the control is pro-
grammed with the Function Codes set as indicated
in Figure 21 with asterisks (*). When the user
changes the values for any or all of the functions,
the new values are stored in the nonvolatile mem-
ory of the counter. This means that the new values
are permanently stored until reprogrammed, even
if power fails.
If it is desired to return the control to the factory set
values after being reprogrammed, enter a value of
“1” in function 43.
FUNCTION
FUNCTION
CODE
ENTRY
CHOICES
DESCRIPTION
CURRENT COUNT VALUE
COUNT KEY
NONE
Shows current count value.
PRESET 1
PRESET 1
KEY
(“1” KEY)
*0 to
999,999
Defines Preset 1 value.
(Factory set value is zero.)
PRESET 2
PRESET 2
KEY
(“2” KEY)
*0 to
999,999
Defines Preset 2 value.
(Factory set value is zero.)
PRESET 3
PRESET 3
KEY
(“3” KEY)
*0 to
999,999
Defines Preset 3 value.
(Factory set value is zero.)
SCALE FACTOR
(Model 5883-1400 only)
5
0.0001 to
9.9999
*1.0000
Defines scale factor value.
(Factory set value is 1.0000)
COUNT MODE
60
*0
1
1
2
3
Count with separate add (Input 2) and subtract
(Input 1)
Count up (Input 1) with Inhibit control (Input 2)
NOTE: This mode cannot be doubled with
double input.
Quadrature
NOTE: Double input MUST be connected to DC
Common.
Count (Input 1) with up/down control (Input 2)
Double Quadrature
NOTE: Double input MUST be connected to DC
Common.
NOTE: Choices shown with asterisks are the factory set values
Figure 21.
Function Code Programming Table