CABLE CONNECTIONS

Test all power cables prior to connection to the unit
to ensure that conductors or cable insulation has not
been damaged while being pulled into position.
Power cables are to be connected to solderless
screw type lugs located at the top of the bypass
switch. Refer to wiring diagrams supplied with unit
for power termination identification. Verfiy that the
lugs supplied will accommodate the power cables
being used. ATSBI units will accommodate the wire
sizes as noted in Table 1.

DE-ENERGIZE ALL POWER CABLE OR CONTROL
WIRING INTENDED FOR CONNECTION TO THE
UNIT. CONTACT WITH LIVE POWER CONNECTORS
CAN CAUSE SEVERE PERSONAL INJURY OR
DEATH.

Carefully strip insulation from the power cables 
avoiding nicking or ringing of the conductor strands. 
Prepare stripped conductor termination end by
cleaning with a wire brush. If aluminum conductors
are used, apply an appropriate joint compound to
the clean conductor surface area. Tighten cable lugs
to the torque values identifyed on the label affixed
to the unit immediately adjacent to the lugs.

5

I.L. 16913A

WARNING

WIRE SIZE FOR EXTERNAL POWER CABLE CONNECTIONS 
PER PHASE CONNECTION. CU/AL WIRE

RATING

200A - 400A

600A

NORMAL

(1) 3/0 – 750MCM – OR

(2) 400 – 500MCM

(2) 3/0 – 250MCM

EMERGENCY

(1) 3/0 – 750MCM – OR

(2) 400 – 500MCM

(2) 3/0 – 250MCM

LOAD

(1) 3/0 – 750MCM – OR

(2) 400 – 500MCM

(2) 3/0 – 250MCM

NEUTRAL**

(3) 3/0 – 750MCM

(6) No. 4 – 500MCM

GROUND

(1) No. 14 – 1/0

(1) No. 14 – 1/0

(1) No. 6 – 2/0

(1) No. 6 – 2/0

RATING

240V 100 - 200A

800 - 1000A

480 - 600V 100 - 150A

NORMAL

(1) No. 6 – 300MCM

(4) 4/0 – 500MCM

EMERGENCY

(1) No. 6 – 300MCM

(4) 4/0 – 500MCM

LOAD

(1) No. 6 – 300MCM

(4) 4/0 – 500MCM

NEUTRAL

(1) No. 6 – 300MCM

(12) 4/0 – 500MCM

GROUND

(1) No. 14 – 1/0

(1) No. 14 – 1/0

(1) No. 6 – 2/0

(1) No. 6 – 2/0

Table 1

Summary of Contents for Cutler-Hammer BIHI

Page 1: ...IN INTERLOCKS AND SAFETY FEATURES INTENDED TO PROVIDE SAFE AND PROPER OPERATING SEQUENCES TO PROTECT PERSONNEL ASSOCIATED WITH THE INSTALLATION OPERATION AND MAINTENANCE OF THIS EQUIPMENT THE FOLLOWI...

Page 2: ...ontacting the factory for technical support A ratings nameplate will also be affixed to the switch identifying the withstand interrupting and closing ratings for which the unit is intended DO NOT APPL...

Page 3: ...ency bypass switches are provided to permit bypass to either power source but both bypass switches are interlocked with the isolation switch to positively prevent inadvertent paralleling of sources IN...

Page 4: ...Effective July 2007 3 I L 16913A Fig 2 Note For bottom entry add 14 to depth of unit...

Page 5: ...4 24 610 Single Phase Only DIMENSIONS INCHES MM BYPASS ISOLATION ATS 2 3 POLE DIMENSIONS INCHES MM BYPASS ISOLATION ATS 4 POLE Max Max Switch CSA Amps Volts Frame Bypass Frame A B C D E F G H I J 150...

Page 6: ...or ringing of the conductor strands Prepare stripped conductor termination end by cleaning with a wire brush If aluminum conductors are used apply an appropriate joint compound to the clean conductor...

Page 7: ...ition Connect the engine start wires to the RED terminal blocks marked 51A and 52A A contact closes between these terminal blocks when an engine start signal is provided by either the ATS or Bypass lo...

Page 8: ...Effective July 2007 7 Fig 3 I L 16913A...

Page 9: ...Effective July 2007 Supercedes I L 16913 dated February 1991 8 I L 16913A Fig 3...

Page 10: ...position if not already in normal This DOES NOT indicate a presence of voltage on the ATS power panel since the ATS logic panel senses on the line side of the Bypass switch Utilizing a voltmetre meas...

Page 11: ...osition the Generator control selector switch to the auto start position Additional functional load transfer tests may be desirable including automatic engine start operation See ATS Controller Manual...

Page 12: ...a downstream short circuit condition the ATS logic will engage the Transfer Mechanism to electrically reset the automatically opened switch If optional overcurrent protection option 16 17 or 37 is pro...

Page 13: ...us short circuit releases are replaced with conventional circuit breakers equipped with thermal elements in addition to magnetic releases to provide overload and short circuit protection to connected...

Page 14: ...ntenance agreements for our ATSBI product In most instances such maintenance agreements also extends warranty periods Contact your local Cutler Hammer Representative for more information on factory su...

Reviews: