background image

These instructions are not complete and may not
contain all of the relevant information necessary
to diagnose or solve a particular problem you
face. If you have any question concerning the
correct operation or maintenance procedures,
please contact your local Cutler-Hammer
representative.

There are no understandings, agreements,
representations, or warranties expressed or
implied including warranties of merchantability
or fitness for a particular purpose other than
those specifically set forth in any separate
contract between the parties. Any such contract
states the sole obligations of Cutler-Hammer and
the contents of this document are not intended
to and shall not become part of or in any way
modify the terms set forth in such a contract.
Information in this literature is intended to be
comprehensive but not all inclusive. Should
further information be required, please contact
the nearest Cutler-Hammer sales office.

IDENTIFICATION

Each Cutler-Hammer ATSBI Switch is supplied with a
permanently affixed nameplate which provides the
user with data on that specific unit. The switch may
only be applied within the limits identified on this
nameplate without additional modification. The
catalogue number appearing on the nameplate will
provide the user with the following application
information:

The nameplate will also list the shop order number/
style number of the unit which should be referenced
when contacting the factory for technical support.

A ratings nameplate will also be affixed to the
switch identifying the withstand, interrupting, and
closing ratings for which the unit is intended.

DO NOT APPLY THIS PRODUCT AT RATINGS
WHICH EXCEED THE VALUES NOTED ON THE
RATINGS LABEL OF THIS UNIT. EXCEEDING THE
NOTED RATINGS CAN CAUSE DEATH, SERIOUS
PERSONAL INJURY OR PROPERTY DAMAGE.

DESCRIPTION

The Combination Bypass Isolation and Transfer
Switch is a completely factory assembled and tested
apparatus used in conjunction with standby power
distribution equipment to provide alternate power
availability to critical load circuits in the event or
primary power interruption and or required
maintenance activity.

It consists of three (3) basic elements. (See Fig. 1.)

1. Automatic Transfer Switch (ATS)

The ATS performs the function of monitoring both
normal and standby power sources and
accomplishing an automatic transfer of critical load
circuits between these sources as dictated by
source availability. The normal source will be the
preferred source and the ATS will remain connected
to this source if available. The ATS consists of three
basic elements:

Effective July 2007

1

I.L. 16913A

Switch Type

BIHI/5BIH3/5BIHI/4BIH3/4BIHI

Combination 

Bypass 

Isolation and 

Transfer Switch

No. of 

Switched 

Poles

2 = 2 Pole
3 = 3 Pole
4 = 4 Pole

Ampere

Rating

0400

0100 = 100A
0150 = 150A
0225 = 225A

0300 = 300A
0400 = 400A
0600 = 600A
0800 = 800A

1000 = 1000A

Voltage

X

A = 120V

B = 208V

W = 240V

X = 480V

E = 600V

G = 220V

M = 230V

Z = 365V

H = 380V

N = 401V
O = 415V

Switch

Frame

F = F Frame

K = K Frame

L = L Frame

M = M Frame

N = N Frame

Enclosure

Type

S

S = Nema 1

U

U = UL

C = CSA

WARNING

Summary of Contents for Cutler-Hammer BIHI

Page 1: ...IN INTERLOCKS AND SAFETY FEATURES INTENDED TO PROVIDE SAFE AND PROPER OPERATING SEQUENCES TO PROTECT PERSONNEL ASSOCIATED WITH THE INSTALLATION OPERATION AND MAINTENANCE OF THIS EQUIPMENT THE FOLLOWI...

Page 2: ...ontacting the factory for technical support A ratings nameplate will also be affixed to the switch identifying the withstand interrupting and closing ratings for which the unit is intended DO NOT APPL...

Page 3: ...ency bypass switches are provided to permit bypass to either power source but both bypass switches are interlocked with the isolation switch to positively prevent inadvertent paralleling of sources IN...

Page 4: ...Effective July 2007 3 I L 16913A Fig 2 Note For bottom entry add 14 to depth of unit...

Page 5: ...4 24 610 Single Phase Only DIMENSIONS INCHES MM BYPASS ISOLATION ATS 2 3 POLE DIMENSIONS INCHES MM BYPASS ISOLATION ATS 4 POLE Max Max Switch CSA Amps Volts Frame Bypass Frame A B C D E F G H I J 150...

Page 6: ...or ringing of the conductor strands Prepare stripped conductor termination end by cleaning with a wire brush If aluminum conductors are used apply an appropriate joint compound to the clean conductor...

Page 7: ...ition Connect the engine start wires to the RED terminal blocks marked 51A and 52A A contact closes between these terminal blocks when an engine start signal is provided by either the ATS or Bypass lo...

Page 8: ...Effective July 2007 7 Fig 3 I L 16913A...

Page 9: ...Effective July 2007 Supercedes I L 16913 dated February 1991 8 I L 16913A Fig 3...

Page 10: ...position if not already in normal This DOES NOT indicate a presence of voltage on the ATS power panel since the ATS logic panel senses on the line side of the Bypass switch Utilizing a voltmetre meas...

Page 11: ...osition the Generator control selector switch to the auto start position Additional functional load transfer tests may be desirable including automatic engine start operation See ATS Controller Manual...

Page 12: ...a downstream short circuit condition the ATS logic will engage the Transfer Mechanism to electrically reset the automatically opened switch If optional overcurrent protection option 16 17 or 37 is pro...

Page 13: ...us short circuit releases are replaced with conventional circuit breakers equipped with thermal elements in addition to magnetic releases to provide overload and short circuit protection to connected...

Page 14: ...ntenance agreements for our ATSBI product In most instances such maintenance agreements also extends warranty periods Contact your local Cutler Hammer Representative for more information on factory su...