Instruction Booklet
Page
28
Effective: October 2014
ATC-300/900 40-400A (480/600Vac)
3-Postion Contactor Based Transfer Switch
Figure 20. ATC-300+ Logic (Utility Supplying Load).
Step 6:
To view the setpoints, press the
<Step/Enter>
pushbut-
ton and enter the Password.
Note:
The factory default Password is 0300. Once all installation and
testing is complete, the Password should be changed by authorized
personnel to a unique Password for the equipment.
After entering the password, press the
<Step/Enter>
pushbutton until the VIEW SETPOINTS menu appears.
Select YES. Press the
<Step/Enter>
pushbutton to
scroll through the setpoints.