Operation

The operating torque is less than 35 ft-Ibs (47 Nm). During 

transformer assembly, it is recommended to operate the 

switch one complete cycle (in each direction), after fluid fill.
Sectionalizing loadbreak switches rotate 360° in either 

direction for alternate source selection. An externally-

installed index plate prevents rotation to positions other 

than the one desired. The switch cannot be switched more 

than one position without resetting the index plate.
A spring-loaded activating mechanism ensures quick 

loadbreak action and positive contact engagement trough all 

positions. Switching can be accomplished in less than one 

cycle, and should be performed with a hotstick.
Using a clampstick leverage tool (P/N CS125UFLTOOL) with 

an Eaton's Cooper Power series Fit-On™ head clampstick 

provides operators with increased level of mechanical 

advantage when performing switching operations.
When switching (with hotstick) from one position to the 

next, (for example: in Figure 7 “line A & B” to position 

“line A only”), the limit plate should be located on the pin 

between the origin and the destination.
Turn hotstick handle, in a rapid motion, until switch has 

fully indexed into the next position. If for any reason, the 

switching operation cannot be completed with a single 

motion, it is acceptable to relax, regrip the hotstick and 

complete the operation by moving the switch handle in the 

same direction

 as the original effort. 

ote:

N

Do not reverse the direction of the switching 

operation before completing the rotation to the next 

position. Reversing direction prior to completing the 

rotation to the next position could jam the mechanism, 

making the switch inoperable.

If the handle stops (jams) in a position between 

the designated (marked) positions, stop switching 

operation and consult the factory prior to 

reattempting operation of the switch.

Figure 8. Hole and coupling placement detail (required 

for Bolt-In design).

Notes:

Hole and coupling placement detail. Couplings not included with switch. 
Pre-Welded coupling plates available. Order P/N 2037424C02M.
All couplings and pins to be welded flat within an angularity tolerance of ± 

one half degree. Weld pins should not be used with optional pad-lockable 

handle.

2.750"

(70 mm)

4.375"

(111 mm)

1.5"

(38.1 mm)

TYPICAL

 .140"

(4 mm)

RADIUS

1.5"

(38.1 mm)

TYPICAL

.662"

(17 mm)

1.375"

(35 mm)

TYPICAL

2.187"

(56 mm)

TYPICAL

 ON INSIDE WALL:

COUPLING WITH INTERNAL TAPPED THREAD 

3/8 – 16 x .75 LONG OR

10M x 19 mm LONG

 ON OUTSIDE WALL:

.315" DIAMETER    x    .630" LONG

       (8 mm)                     (16 mm)

      WELD PIN

1.320" +

0.030

- 0.000

(33.5 mm 

+0.8)

- 0.0

DIA. HOLE

 WARNING 

Enclosed “Warning” decal (P/N 1139596B02) must be 

displayed at or near operating handle of switch as 

a warning to service personnel. Failure to do so will 

constitute a waiver of all warranty and indemnity 

obligations which may be attributable to Eaton's Cooper 

Power Systems Division.

 WARNING 

The misapplication of the switch constitutes a potential 

hazard to life and property. Accordingly, the user must 

exercise due care in utilizing these instructions to assure 

that the switch is properly applied.

 CAUTION 

Enclosed decal (P/N 1109699A) should be displayed at or 

near operating handle of switch as a warning to service 

personnel. Failure to do so will constitute a waiver of 

all warranty and indemnity obligations which may be 

attributable to Eaton's Cooper Power Systems Division.

8

SECTIONALIZING SWITCH INSTALLATION INSTRUCTIONS

  MN800002EN   March 2016

Summary of Contents for COOPER POWER LS4R Series

Page 1: ...Sectionalizing switch installation instructions COOPER POWER SERIES OEM Equipment MN800002EN Effective March 2016 Supersedes June 2015...

Page 2: ...IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES...

Page 3: ...Std C37 71 2001 standard 2 Ratings and characteristics table per IEC 60265 1 2 Dimensional information 2 INSTALLATION PROCEDURE Bolt In assembly 4 Ring Mount assembly 5 Connect internal leads 6 RECOM...

Page 4: ...n Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low v...

Page 5: ...aded activating mechanism ensures quick loadbreak action and positive contact engagement through all positions The Make Before Break MBB switches provide uninterrupted power during switching Read this...

Page 6: ...n phases kV 95 125 150 Across open contacts kV 95 125 150 Power Frequency 1 minute To ground and between phases kV 35 60 70 Across open contacts kV 35 60 70 DC Withstand 15 minutes To ground and betwe...

Page 7: ...n be used on 14 gauge 075 inch 1 9 mm to 25 inch 6 4 mm thick frontplate 14 gauge shown 3 Optional padlock handle is available See catalog section CA800005EN Table 6 and Figure 6 4 See catalog section...

Page 8: ...ng is accomplished with O rings on the operating shaft and gasketed sealing gland secured on the outside of the tank with locking nut 5 Optional install spring small end toward end of shaft and limit...

Page 9: ...ance zone and have an insulated barrier between them and the switch This barrier will deflect any gas bubbles generated by the switch operation The outline drawing shown in Figure 6 describes the swit...

Page 10: ...B A A A A COIL B C COIL C COIL V BLADE MAKE BEFORE BREAK A C B A C B A C B A C B AB C B C OPEN A C LINES A B TO C LINE A ONLY LINE B ONLY TO C TO C OPEN ALL B A C COIL T BLADE BREAK BEFORE MAKE A C B...

Page 11: ...d training may cause excess cantilever force and difficulty in switch operation Figure 6 Arc clearance zone Figure 7 View of tank front with optional limit plate positioned over pin Note With limit pl...

Page 12: ...next position could jam the mechanism making the switch inoperable If the handle stops jams in a position between the designated marked positions stop switching operation and consult the factory prio...

Page 13: ...adbreak devices Failure to follow this warning could result in equipment damage severe injury or death WARNING Hazardous voltage Do not operate loadbreak equipment if a fault condition is suspected Do...

Page 14: ...This page is intentionally left blank 10 SECTIONALIZING SWITCH INSTALLATION INSTRUCTIONS MN800002EN March 2016...

Page 15: ...This page is intentionally left blank 11 SECTIONALIZING SWITCH INSTALLATION INSTRUCTIONS MN800002EN March 2016...

Page 16: ...es Eaton com cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No MN800002EN Rev 01 Supersedes MN800002EN Rev 00 SAFETY FOR LIFE Eaton is a registered trademark All trademark...

Reviews: