background image

Ring-mount assembly (LS4R--- and LS4E---)

ote:

N

The tank wall should have a 1.325" (34 mm) diameter 

hole with an anti-rotation key (refer to Figure 8). Switch 

should be located to ensure recommended clearances 

in Figure 6 are maintained.

ote:

N

Recommended socket for securing the locking nut is a 

6 point, 1 

3

/

4

" socket with a minimum socket depth of 

1

/

2

" (38 mm).

1.  Install the gasket over the threaded switch boss (with 

integral sealing gland) and insert through the tank hole. 

(Note: make sure gasket’s sealing surface is clean and 

the gasket properly seated.)

2.  Position the switch with the open sides of the switch 

block on the bottom and on the side.

3.  Assemble and tighten furnished locking hex nut to the 

recommended torque in Table 7.

4.  (Optional) install spring (small end out) and index (limit) 

plate over the shaft.

5.  Install handle onto the switch shaft with the stainless 

steel hex socket cap screw and lock washer supplied 

and tighten to recommended torque in Table 5.

Connect internal leads

1.

  Connect internal leads

 to the switch contacts with 

3/8" or (10 mm) hardware, (not supplied). (Max. cable 

connections 500 MCM or 240 mm

2

). Use torque values 

recommended by fastener manufacturers. Apply torque 

to the fasteners, not to the switch terminals. See Table 

6 for recommended wiring schematics.

Recommended clearances

Mechanical 

 

External handle must be clear of obstruction. Clearances 

are also required for hook-stick operation.

Dielectric (under-oil)

 

It is not recommended that other components be located 

above the switch, since clouds of gas rise during switch 

operation. If such an arrangement cannot be avoided, the 

components should, at a minimum, be located outside 

the arc clearance zone and have an insulated barrier 

between them and the switch. This barrier will deflect any 

gas bubbles generated by the switch operation.

The outline drawing shown in Figure 6 describes the switch 

and its application to oil-filled apparatus. This information 

should be used only by trained personnel familiar with the 

design requirements for oil-filled apparatus. This information 

is not intended as a substitute for adequate training and 

experience in such design. Should clarification or further 

information be required for the user’s purposes, contact 

your Eaton representative.
All energized parts of the switch must be under oil and 

spaced away from other energized parts or ground with 

sufficient distance to withstand all operating and test 

voltages. In order for proper switch operation to occur, an 

arc clearance zone is required around the switch. This zone 

should be under oil and free of all foreign materials. See 

Figure 6.

Table 5.  Recommended Torque (Ring-Mount)

Part

Torque Level

Locking Nut

40-60 ft-lbs (54-82 Nm)

Switch Handle Screw

40-60 in-lbs (5-7 Nm)

Figure 5.  Four-Position Ring-Mount loadbreak switch 

(top/side view).

MOUNTING RING

(FURNISHED)

TANK SEALING GLAND

AND GASKET

(FURNISHED)

SWITCH BODY

(2 SPRING SHOWN)

HEX NUT

(FURNISHED)

TANK WALL

4 WELD PINS

SEE FIGURE 10

(NOT FURNISHED)

LIMIT PLATE

(FURNISHED)

SPRING

(FURNISHED)

HANDLE

(FURNISHED)

LOCKWASHER

(FURNISHED)

CAP SCREW

HEX SOCKET

(FURNISHED)

 WARNING 

All leads, connections and contact blades must remain 

under oil. Failure to do so could cause arcing which 

may result in component failure, property damage or 

possible severe personal injury.

 WARNING 

Recommended (minimum) under-oil clearances must be 

followed to avoid internal arcing which could result in 

component failure, property damage or possible severe 

personal injury.

5

SECTIONALIZING SWITCH INSTALLATION INSTRUCTIONS

  MN800002EN   March 2016

Summary of Contents for COOPER POWER LS4R Series

Page 1: ...Sectionalizing switch installation instructions COOPER POWER SERIES OEM Equipment MN800002EN Effective March 2016 Supersedes June 2015...

Page 2: ...IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES...

Page 3: ...Std C37 71 2001 standard 2 Ratings and characteristics table per IEC 60265 1 2 Dimensional information 2 INSTALLATION PROCEDURE Bolt In assembly 4 Ring Mount assembly 5 Connect internal leads 6 RECOM...

Page 4: ...n Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low v...

Page 5: ...aded activating mechanism ensures quick loadbreak action and positive contact engagement through all positions The Make Before Break MBB switches provide uninterrupted power during switching Read this...

Page 6: ...n phases kV 95 125 150 Across open contacts kV 95 125 150 Power Frequency 1 minute To ground and between phases kV 35 60 70 Across open contacts kV 35 60 70 DC Withstand 15 minutes To ground and betwe...

Page 7: ...n be used on 14 gauge 075 inch 1 9 mm to 25 inch 6 4 mm thick frontplate 14 gauge shown 3 Optional padlock handle is available See catalog section CA800005EN Table 6 and Figure 6 4 See catalog section...

Page 8: ...ng is accomplished with O rings on the operating shaft and gasketed sealing gland secured on the outside of the tank with locking nut 5 Optional install spring small end toward end of shaft and limit...

Page 9: ...ance zone and have an insulated barrier between them and the switch This barrier will deflect any gas bubbles generated by the switch operation The outline drawing shown in Figure 6 describes the swit...

Page 10: ...B A A A A COIL B C COIL C COIL V BLADE MAKE BEFORE BREAK A C B A C B A C B A C B AB C B C OPEN A C LINES A B TO C LINE A ONLY LINE B ONLY TO C TO C OPEN ALL B A C COIL T BLADE BREAK BEFORE MAKE A C B...

Page 11: ...d training may cause excess cantilever force and difficulty in switch operation Figure 6 Arc clearance zone Figure 7 View of tank front with optional limit plate positioned over pin Note With limit pl...

Page 12: ...next position could jam the mechanism making the switch inoperable If the handle stops jams in a position between the designated marked positions stop switching operation and consult the factory prio...

Page 13: ...adbreak devices Failure to follow this warning could result in equipment damage severe injury or death WARNING Hazardous voltage Do not operate loadbreak equipment if a fault condition is suspected Do...

Page 14: ...This page is intentionally left blank 10 SECTIONALIZING SWITCH INSTALLATION INSTRUCTIONS MN800002EN March 2016...

Page 15: ...This page is intentionally left blank 11 SECTIONALIZING SWITCH INSTALLATION INSTRUCTIONS MN800002EN March 2016...

Page 16: ...es Eaton com cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No MN800002EN Rev 01 Supersedes MN800002EN Rev 00 SAFETY FOR LIFE Eaton is a registered trademark All trademark...

Reviews: