60
10 Maintenance / Checking
MANUAL CEAG AUtoMAtiC tEst systEM At-s
+
40071860177 (C) December 2016 www.ceag.de
10 Maintenance / Checking
10.1 Safety Notes
WARNING! RISK OF INJURY!
Improper maintenance work can cause serious per-
sonal injury and / or material damage . This work has
to be performed only by authorised, skilled and ade-
quate personnel who have received instructions pro-
viding information on the device and in observance
of local safety regulations .
•
Before working on and with the system switch it off and
protect it against reset.
•
Do not touch the system unti its temperature is as high
as the ambient temperature.
10.2 General information to
maintenance / checking
The carrying out of the safety inspections as required
by statutes and directives has to be made regularly. The
operator of the emergency lighting system is responsible
for organising and supervising this work!
The following information must be specified in writing and
made available at all times :
•
The nature and extent of the work
•
Recording of work results
•
Responsibilities and permits for carrying out the work
– which persons may carry out which operations?
– which persons are responsible for supervising the
work?
•
Duties of reporting (e. g. in the case of faults or function
tests)
•
Organisational measures when working on the Auto-
matic Test System. This may include:
– Duties of information and reporting on the start, dura-
tion and end of the work
– Safety measures while the work is being carried out:
e. g. standby lighting, power supply isolation and lock-
out (e. g. removing the fuses, key-operated switch,
safety signage)
– Safety equipment for the personnel carrying out the
work on the plant (e. g. suitable work clothing and
personal protection equipment)
– Safety equipment providing protection from hazards
caused by adjacent plant (e. g. safety grilles, barriers,
making safe or roads)
Maintenance and repair work at the Automatic
Test System can be done by the customer service
of CEAG Notlichtsysteme GmbH at any time . (s .
enclosed Customer Service Order) .
Our customer service locations can be found all over
Germany, see the enclosed map „Addresses: CEAG
Customer Service“.
In addition, we offer you a
Maintenance Contract for
Emergency Lighting
making organisation easier to you!
This contract contains the annual checking and includes
the following work:
– Testing of mains/emergency light switching
function of devices
– Visual check of electrical equipment
– Mechanical check at the devices
– Operational test of other electronics
– Checking of lamps only for luminaires with
CG-monitoring
Not included in maintenance services is repair and
overhaul work, in particular the replacement of defective
electronics or defective light sources.
NOTE
In case of returns you need a RMA number from us.
For further information see www.ceag.de!