3. Technical Data
MANUAL CEAG AUtoMAtiC tEst systEM At-s
+
40071860177 (C) December 2016 www.ceag.de
250
800
600
3.3 Data Sheet for AT-S
+
C4
Type of system
AT-S
+
C4
Construction
Sheet steel cabinet with partial
viewing window in the door
Height
800 mm
Width
600 mm
Depth
250 mm
Weight
approx. 80 kg
Insulation class
I
Degree of protection
IP 54
External painting
Structure powder laquer RAL 7035
light grey
Cable entry
at the top (prepunched roof sheeting)
Hinge
right
Mains rated voltage
400V AC, 50/60 Hz
Ambient temperature operation (please
attend to the attachted operating and
installation instructions)
-5°C up to +35°C
Mains feed in (max. 50 mm²) L1, L2, L3
Q1, X14, X12
Max. 8 circuits (max. 4 mm²)*
X2.1
Marshalling mains (max. 16 mm²)
F10 - F15
Addresses optional places DLS-3Ph, TLS
(max. 2.5 mm²)
customised
Connection to ext. control switch
(max. 4 mm²)
X1.1.S1-S2
Connection to 24V current loop
(max. 4 mm²)
X1.1.S3-S4
Connection to potential-free signal
contacts (max. 4 mm²)
X1.1.C0 14; 12; 24; 22; 34; 32/C1
44; 54
Connection to CG-S Bus (max. 4 mm²)
X1.1.A-B
Connection to RS485 Bus (max. 4 mm²)
X1.1.RS485.A-B
Connection to 24V analog output
(max. 4 mm²)
X1.1.+24V Out--24V Out
Connection to 24V analog input
(max. 4 mm²)
X1.1.Z1.1-Z1.2/Z2.1-Z2.2/Z3.1-Z3.2/
Z4.1-Z4.2
* Max. 2.5mm² flexible with wiring sleeve. The final circuits get wired customised.
Interior side view, left
Interior side view, right
Front view, open