75
ARCON 3G
ARCON 3G MANUAL
MN026015EN October 2020 www.eaton.com
Prefix Number Text
Description
ACK
Relay
TRIP 1
Relay
TRIP 2
Relay
TRIP 3
Relay
Trip alarm
Relay
Watchdog
LED System
LED TRIP
LED RUN
9
LED TRIP
10
IGNITION PIN
1
RESTART
System starting.
NO
OPEN
OPEN
OPEN
OPEN
OPEN
OFF
OFF
OFF
OFF
RESET
3
START ADDRESSING
Addressing process started.
NO
-
-
-
-
-
-
-
-
-
-
E
4
ADDRESSING ERROR
Error detected in addressing process.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
5
ADDRESSING OK
Addressing process finished successfully.
NO
-
-
-
-
-
-
-
-
-
-
E
6
FLASH ACCESS ERROR
Serial flash memory error detected.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
8
START INITIALIZATION
Initialization process started.
NO
-
-
-
-
-
Orange / 2Hz
-
-
-
-
E
9
PARAMETERIZATION ERROR
Error while parameterization process.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
10
PARAMETERIZATION OK
The parameterization process is completed successfully.
NO
-
-
-
-
-
-
-
-
-
-
11
INITIALIZATION FINISHED
Initialization process finished.
NO
-
-
-
-
-
-
-
-
-
-
12
START NORMAL OPERATION MODE
Entering into normal operation mode.
NO
-
-
-
-
CLOSED
Green / 1Hz
-
Green / 1Hz
-
-
T
13
TRIP
Arc protection trip detected.
YES
CLOSED
CLOSED
CLOSED
CLOSED
-
Red / 2Hz
Red
OFF
Red
SET
E
14
WD RESET
On chip watchdog reset happened.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
E
15
ADC ERROR
ADC error detected.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
E
16
DAC ERROR
DAC error detected.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
E
17
PARAMETER ERROR
Parameter error detected.(parameter missing or over range)
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
E
18
SENSOR WIRE FAULT
Sensor wire fault detected.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
E
19
SENSOR CONSTELLATION ERROR
Unexpected sensor detected.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
E
20
INTERLINK ERROR
INTERLINK communication error. (CAN bus error)
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
E
21
INTERLINK CONSTELLATION ERROR
INTERLINK module missing or unexpected module detected.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
E
22
INTERLINK COMPATIBILITY ERROR
INTERLINK compatibility error.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
E
24
UPF ERROR
User parameter file (UPF) missing or corrupted.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
E
25
MPF ERROR
Manufacture parameter file (MPF) missing or corrupted.
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
26
PARAMETER CHANGED
Parameter change detected.
NO
-
-
-
-
-
-
-
-
-
-
27
USER MODE
Entering into user mode.
NO
-
-
-
-
-
-
-
-
-
-
28
PROTECTED MODE
Entering into password protected mode.
NO
-
-
-
-
-
-
-
-
-
-
29
MANUFACTURER MODE
Entering into manufacturer mode.
NO
-
-
-
-
-
-
-
-
-
-
E
30
ICOM ERROR
iCOM communication error. (CAN bus error).
YES
-
-
-
-
OPEN
Red / 2Hz
-
-
-
-
Proof 1 — October 29, 2020 3:00 PM