The Master MAIN has a simple HMI which can be used in normal operation mode.
At the start of normal operation mode, the display is turned off and it stays off until a
system error or trip event occurs. After acknowledging all system errors, the display will
turn off again.There are two types of events which require acknowledgment in the normal
operation mode:
•
SYSTEM
•
TRIP
System error
More than one system error may occur in the system. All system errors will be written
in the Event logger and each of them must be acknowledged by user in chronological
order.Error codes are presented as E.XX
6
. If user presses and holds INFO button
following additional information are alternately shown at intervals of 2 seconds:
•
Affected module M.XX
7
•
Affected sensor S.XX
8
When user releases INFO button the error code is shown again. User can acknowledge
the displayed system error by pressing ACK button.
TRIP
Trip is presented by event
“T .13” .
The TRIP event is written in the Event logger and must
be acknowledged by user. If user presses and holds INFO button following additional
information are alternately shown at intervals of 2 seconds:
•
Affected module M.XX
7
•
Affected sensor S.XX
8
When user releases INFO button the trip code is shown again. User can acknowledge
the displayed trip by pressing ACK button.
Figure 3.5 Master MAIN – Internal HMI
6
XX = EVENT NUMBER
7
XX = MODULE ADDRESS
8
XX = SENSOR NUMBER
Internal HMI