INSTALLATION
EATON
9130 (9910-E15/E16) UPS Installation Guide for IBM
®
Applications
S
164201783 Rev 2
13
Remote Emergency Power-off
REPO is used to shut down the UPS from a distance. This feature can
be used for shutting down the load and the UPS by thermal relay, for
instance in the event of room overtemperature. When REPO is
activated, the UPS shuts down the output and all its power converters
immediately. The UPS remains on to alarm the fault.
W
A
R
N
I
N
G
The REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be
separated from any hazardous voltage circuits by reinforced insulation.
C
A
U
T
I
O
N
S
The REPO must not be connected to any utility connected circuits. Reinforced insulation
to the utility is required. The REPO switch must have a minimum rating of 24 Vdc and
20 mA and be a dedicated latching-type switch not tied into any other circuit. The REPO
signal must remain active for at least 250 ms for proper operation.
S
To ensure the UPS stops supplying power to the load during any mode of operation, the
input power must be disconnected from the UPS when the emergency power-off function
is activated.
NOTE
For Europe, the emergency switch requirements are detailed in Harmonized
document HD-384-48 S1, “Electrical Installation of the Buildings, Part 4: Protection for Safety,
Chapter 46: Isolation and Switching.”
REPO Connections
Wire Function
Terminal Wire Size Rating
Suggested Wire Size
REPO
L1
4–0.32 mm
2
(12–22 AWG)
0.82 mm
2
(18 AWG)
L2
NOTE
Leave the REPO connector installed in the REPO port on the UPS even if the REPO
function is not needed.
Summary of Contents for 9910-E16
Page 2: ...This page intentionally left blank ...
Page 3: ...Eaton 9130 9910 E15 E16 UPS Installation Guide for IBM Applications ...
Page 31: ...Eaton 9130 9910 E15 E16 UPS Asennusopas IBM sovelluksille ...
Page 60: ...Onduleur 9910 E15 E16 Eaton 9130 Guide d Installation pour Applications IBM ...
Page 91: ...Eaton 9130 9910 E15 E16 USV Installationshandbuch für IBM Anwendungen ...
Page 120: ...UPS Eaton 9130 9910 E15 E16 Guida all installazione per applicazioni IBM ...
Page 149: ...Zasilacz UPS Eaton 9130 9910 E15 E16 Instrukcja instalowania dla zastosowań IBM ...
Page 182: ...ИБП Eaton 9130 9910 E15 E16 Руководство по установке в системах IBM ...
Page 215: ...SAI Eaton 9130 9910 E15 E16 Guía de instalación para aplicaciones IBM ...
Page 244: ...Eaton 9130 9910 E15 E16 UPS Installationshandledning för IBM applikationer ...