8.
Press the
button on the UPS front panel for at least one second.
The UPS front panel display changes status to “UPS starting...”
9.
Check the UPS front panel display for active alarms or notices.
Resolve any active alarms before continuing. See
“Troubleshooting” in the UPS user's guide.
If the
indicator is on, do not proceed until all alarms are clear.
Check the UPS status from the front panel to view the active
alarms. Correct the alarms and restart if necessary.
10.
Verify that the
indicator illuminates solid, indicating that the
UPS is operating normally and any loads are powered.
The UPS should be in Normal mode.
11.
Press the
ESC
button until the start screen appears.
12.
If optional EBMs are installed, see “Configuring the UPS for EBMs”
on page 24 to set the number of installed EBMs.
13.
To change other factory-set defaults, see the “Operation” section.
NOTE
IBM recommends setting the date and time.
NOTE
At initial startup, the UPS sets system frequency according to input line frequency
(input frequency auto-sensing is enabled by default). After initial startup, auto-sensing is
disabled until manually re-enabled by output frequency setting.
NOTE
At initial startup, input voltage auto-sensing is disabled by default. When manually
enabled by output voltage setting, at the next AC startup the UPS sets output voltage
according to input line voltage. After the subsequent startup, auto-sensing is disabled until
manually re-enabled by output voltage setting.
14.
If you installed an optional REPO, test the REPO function:
Activate the external REPO switch. Verify the status change on the
UPS display.
Deactivate the external REPO switch and restart the UPS.
Summary of Contents for 9910-E16
Page 2: ...This page intentionally left blank ...
Page 3: ...Eaton 9130 9910 E15 E16 UPS Installation Guide for IBM Applications ...
Page 31: ...Eaton 9130 9910 E15 E16 UPS Asennusopas IBM sovelluksille ...
Page 60: ...Onduleur 9910 E15 E16 Eaton 9130 Guide d Installation pour Applications IBM ...
Page 91: ...Eaton 9130 9910 E15 E16 USV Installationshandbuch für IBM Anwendungen ...
Page 120: ...UPS Eaton 9130 9910 E15 E16 Guida all installazione per applicazioni IBM ...
Page 149: ...Zasilacz UPS Eaton 9130 9910 E15 E16 Instrukcja instalowania dla zastosowań IBM ...
Page 182: ...ИБП Eaton 9130 9910 E15 E16 Руководство по установке в системах IBM ...
Page 215: ...SAI Eaton 9130 9910 E15 E16 Guía de instalación para aplicaciones IBM ...
Page 244: ...Eaton 9130 9910 E15 E16 UPS Installationshandledning för IBM applikationer ...