INSTALLATION
EATON
9130 (9910-E15/E16) UPS Installation Guide for IBM
®
Applications
S
164201783 Rev 2
11
6.
If you are installing power management software, connect your
computer to one of the communication ports or optional
connectivity card. For the communication ports, use an appropriate
cable as follows:
S
For the AS/400.
Use the supplied AS/400 communication cable.
The “AS/400” end of the cable connects to the port marked
“J14” or “UPS”on the AS/400 rear panel.
S
For PCs and workstations.
Use the communication cable supplied
with the power management software CD.
7.
If an emergency power-off (disconnect) switch is required by local
codes, see “Remote Emergency Power-off” (REPO) on page 13 to
install the REPO switch before powering on the UPS.
8.
If you are installing EBM(s), continue to the following section,
“Connecting the EBM(s).” Otherwise, continue to “Starting the
UPS” on page 22.
Connecting the EBM(s)
To install the optional EBM(s) for a UPS:
1.
On the rear of the UPS, remove the cable retention clip covering
the battery connector. Retain the clip and screws. See Figure 3.
2.
Installations with one EBM only.
Remove the cable retention clip
covering the right battery connector. Retain the clip and screws.
3.
Installations with more than one EBM.
For all EBMs except the last
EBM, remove the cable retention clips covering both battery
connectors. Do not remove the clip from the second battery
connector on the last EBM. Retain the clips and screws.
C
A
U
T
I
O
N
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and
will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and
firmly.
4.
Plug the EBM cable(s) into the battery connector(s) as shown in
Figure 3. Up to four EBMs may be connected to the UPS.
5.
For each cable retention clip removed, rotate the clip and install it
under each EBM cable connection using the retained screws.
Summary of Contents for 9910-E16
Page 2: ...This page intentionally left blank ...
Page 3: ...Eaton 9130 9910 E15 E16 UPS Installation Guide for IBM Applications ...
Page 31: ...Eaton 9130 9910 E15 E16 UPS Asennusopas IBM sovelluksille ...
Page 60: ...Onduleur 9910 E15 E16 Eaton 9130 Guide d Installation pour Applications IBM ...
Page 91: ...Eaton 9130 9910 E15 E16 USV Installationshandbuch für IBM Anwendungen ...
Page 120: ...UPS Eaton 9130 9910 E15 E16 Guida all installazione per applicazioni IBM ...
Page 149: ...Zasilacz UPS Eaton 9130 9910 E15 E16 Instrukcja instalowania dla zastosowań IBM ...
Page 182: ...ИБП Eaton 9130 9910 E15 E16 Руководство по установке в системах IBM ...
Page 215: ...SAI Eaton 9130 9910 E15 E16 Guía de instalación para aplicaciones IBM ...
Page 244: ...Eaton 9130 9910 E15 E16 UPS Installationshandledning för IBM applikationer ...