Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
Table 17. Recommended Input and Bypass Circuit Breaker Ratings
Input Rating
UPS Model
UPS Rating
Load Rating
208V
220V
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1)
10 kW
80% Rated
45A
45A
100% Rated
40A
35A
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1)
20 kW
80% Rated
90A
90A
100% Rated
80A
70A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1)
30 kW
80% Rated
150A
150A
100% Rated
110A
110A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1)
40 kW
80% Rated
200A
175A
100% Rated
150A
150A
Eaton 93PM-L 60-3
50 kW
80% Rated
225A
225A
100% Rated
200A
175A
Eaton 93PM-L 60-3
60 kW
80% Rated
300A
300A
100% Rated
225A
225A
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings
from
in accordance with the NEC, ANSI/NFPA 70.
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load shown in
through . The recommended line-to-line load unbalance is 50% or
less.
Output overcurrent protection and Output disconnect switches are to be supplied by the customer.
lists the recommended rating for output circuit breakers.
!
IMPORTANT
If an output breaker is not provided, the wire between the output and the load must be sized the same as the
bypass input wire.