Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
Power wiring terminals E1 through E11 are 2-hole bus bar mountings for standard NEMA 2-hole barrel lugs.
The power wiring connections for this equipment are rated at 90°C. See
for external power cable
terminations,
for supplied external wiring terminal hardware, and
for recommended
installation parts and tools not supplied by Eaton.
and
, show the location of the UPS power cable terminals.
For a detailed view of the power terminals for the 2, 3 and 4-Breaker SIAC-B configurations, see
for
the 2–Breaker SIAC-B,
for the 3–Breaker SIAC-B, and
for the 4–Breaker SIAC-B.
Table 13. UPS External Power Cable Terminations
Terminal Function
Terminal
Function
Bus Landings
(using back-to-
back lugs)
Tightening Torque
Nm (lb in)
Screw Size and
Type
AC Input to UPS
Rectifier
E1
Phase A
4 – 2 bolt mounting
35 (310)
M12 Hex
E2
Phase B
4 – 2 bolt mounting
35 (310)
M12 Hex
E3
Phase C
4 – 2 bolt mounting
35 (310)
M12 Hex
AC Input to Bypass
E6
Phase A
4 – 2 bolt mounting
35 (310)
M12 Hex
E7
Phase B
4 – 2 bolt mounting
35 (310)
M12 Hex
E8
Phase C
4 – 2 bolt mounting
35 (310)
M12 Hex
E12
Neutral
8 – 2 bolt mounting
35 (310)
M12 Hex
AC Output to Critical
Load
E9
Phase A
4 – 2 bolt mounting
35 (310)
M12 Hex
E10
Phase B
4 – 2 bolt mounting
35 (310)
M12 Hex
E11
Phase C
4 – 2 bolt mounting
35 (310)
M12 Hex
E12
Neutral
8 – 2 bolt mounting
35 (310)
M12 Hex
DC Input from Battery
E4
Battery (+)
4 – 2 bolt mounting
35 (310)
M12 Hex
E5
Battery (-)
4– 2 bolt mounting
35 (310)
M12 Hex
Customer Ground
Ground
Ground
14 - #14-1/0
pressure termination
5.1 (45)
Slotted
NOTE
Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in
Table 14. Supplied External Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminal Used On
Bolt, Grade 5
M12 x 35 mm
60
Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load
Flat Washer
M12
60
Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load
Conical
Washer
M12
60
Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load
NOTE
For additional information (including part numbers and manufacturer information) and/or assistance contact an Eaton
service representative (see paragraph
).