1.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
2.
Tap the
GO ONLINE
button.
All of the UPSs transfer to Double Conversion mode. If the power module is not available, the system
remains on bypass and an alarm sounds.
The
NORMAL
status indicator is illuminated.
66..44..77
TTrraannssffeerr ffrroom
m EES
SS
S M
Mooddee ttoo D
Doouubbllee C
Coonnvveerrssiioonn M
Mooddee
To transfer the load to Standard Normal mode:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The Control screen is displayed.
2.
Tap the
EAA CONTROLS
tab on the secondary Control menu navigation bar. The
EAA CONTROLS
screen
is displayed.
3.
Tap the
DISABLE ESS
button.
All of the UPSs transfer to Double Conversion mode.
The
NORMAL
status indicator is illuminated.
66..44..88
TTrraannssffeerr ffrroom
m D
Doouubbllee C
Coonnvveerrssiioonn M
Mooddee ttoo EES
SS
S M
Mooddee
To transfer the load to HE Normal mode:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The Control screen is displayed.
2.
Tap the
EAA CONTROLS
tab on the secondary Control menu navigation bar. The
EAA CONTROLS
screen
is displayed..
3.
Tap the
ENABLE ESS
button.
All of the UPSs transfer to ESS mode if no abnormal power conditions are detected. If abnormal power
conditions are detected, the UPSs will wait and transfer to ESS mode when conditions are cleared.
The
NORMAL
status indicator is illuminated.
66..44..99
TTrraannssffeerr ffrroom
m D
Doouubbllee C
Coonnvveerrssiioonn ttoo B
Byyppaassss M
Mooddee aanndd S
Shhuuttddoow
wnn aallll U
UP
PM
Mss
To transfer the critical load to Bypass mode and shutdown the UPMs:
1.
Transfer the critical load to bypass by performing the procedure in paragraph
Transfer from Double Conversion to Bypass Mode
2.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
3.
Tap the
MODULES CONTROLS
tab on the secondary Control menu navigation bar. The UPM Select
screen is displayed.
4.
On the UPM Select screen, select UPM 1. The UPM Control Screen is displayed.
5.
Tap the
SHUTDOWN MODULE
button.
The UPM status indicates SHUTDOWN. The power module is turned off.
Logic power remains on.
6.
Repeat
Step 2
through
Step 5
selecting UPM 2 to shutdown UPM 2.
The UPM status indicates SHUTDOWN. The power module is turned off.
Logic power remains on.
7.
Repeat
Step 2
through
Step 5
selecting UPM 3 to shutdown UPM 3.
The UPM status indicates SHUTDOWN. The power module is turned off.