Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
Table 16. Power Cable Conduit Recommendations
UPS Model
UPS
Rating
Voltage
Terminal
Number
of Wires
in Conduit
Minimum
Conduit
Trade Size
(inches)
Number
of
Conduits
93PM-L 60-1
93PM-L 60-2 (N+1)
10 kW
208 or 220
Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3/4
1
208 Vac
AC Input to UPS Bypass
(A, B, C, Neutral, Ground)
5
1
1
220 Vac
3/4
208 or 220
Vac
AC Output
(A, B, C, Neutral, Ground)
5
3/4
1
DC
Battery
(Positive, Negative, Ground)
3
1/2
1
93PM-L 60-1
93PM-L 60-2 (N+1)
20 kW
208 or 220
Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
1
1
AC Input to UPS Bypass
(A, B, C, Neutral, Ground)
5
1-1/4
1
AC Output
(A, B, C, Neutral, Ground)
5
1-1/4
1
DC
Battery
(Positive, Negative, Ground)
3
1/2
1
93PM-L 60-2
93PM-L 60-3 (N+1)
30 kW
208 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
1-1/4
1
220 Vac
1-1/2
208 or 220
Vac
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
5
2
1
208 Vac
AC Output
(A, B, C, Neutral, Ground)
5
2
1
220 Vac
1-1/4
DC
Battery
(Positive, Negative, Ground)
3
3/4
1
93PM-L 60-2
93PM-L 60-3 (N+1)
40 kW
208 or 220
Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2
1
208 Vac
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
5
2-1/2
1
220 Vac
2
208 or 220
Vac
AC Output
(A, B, C, Neutral, Ground)
5
2
1
DC
Battery
(Positive, Negative, Ground)
3
1
1