UPS Installation Plan and Unpacking
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input
circuit breaker current ratings from Table 3-7 in accordance with local regulations.
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load. The recommended line-to-line load unbalance is 50% or less with reference to
full load.
Readily accessible disconnect devices (Bypass and output overcurrent protection and bypass and output
disconnect switches) are to be supplied by the customer. Table 3-8 lists the Recommended Bypass Circuit
Breaker, Output Circuit Breaker and Bypass Fuse Ratings.
Table 3-8. Recommended Bypass Circuit Breaker, Output Circuit Breaker and Bypass Fuse Ratings
Circuit Breaker Rating
Fuse Parameters
UPS Model
Load Derating
400V
Current/Min
I2T/Max
93E
MK2
-10I-9Ah-MBS
93E
MK2
-15I-9Ah-MBS
93E
MK2
-20I-9Ah-MBS
93E
MK2
-30I-9Ah-MBS
93E
MK2
-40I-9Ah-MBS
80% Derating
18A
100% Rating
14A
80% Derating
27A
100% Rating
22A
80% Derating
36A
100% Rating
29A
80% Derating
54A
100% Rating
43A
80% Derating
72A
100% Rating
58A
20A
10200A
2
Sec
32A
10200A
2
Sec
40A
10200A
2
Sec
63A
10200A
2
Sec
80A
20,400
A
2
Sec
If internal battery option used, UPS default with DC disconnect device by factory default
If external battery option used,
External DC input overcurrent protection and disconnect switch for the remote
battery
location is to be
provided by the user. Table 3-9 lists the maximum rating for continuous-duty rated circuit
breakers satisfying the criteria for both.
Table 3-9. Recommended DC input circuit breaker rating
Circuit Breaker Rating
UPS Model
Load Derating
Bat rated voltage
(
DC432V
)
93E
MK2
-10I-9Ah-MBS
93E
MK2
-15I-9Ah-MBS
93E
MK2
-20I-9Ah-MBS
93E
MK2
-30I-9Ah-MBS
93E
MK2
-40I-9Ah-MBS
80% Derating
100% Rating
23A
80% Derating
100% Rating
34A
80% Derating
100% Rating
46A
80% Derating
100% Rating
69A
80% Derating
100% Rating
92A
16
Eaton 93E
MK2
UPS (10-40kVA, 380/400/415V) Installation and Operation
Summary of Contents for 93E MK2
Page 1: ...Eaton 93E MK2 UPS 10 40 kVA 380 400 415V Installation and Operation Manual...
Page 2: ......
Page 4: ......
Page 8: ......
Page 49: ...Notes 39 Eaton 93E MK2 UPS 10 40kVA 380 400 415V Installation and Operation...
Page 94: ......
Page 95: ......
Page 96: ...614 00389 00...