Product Specifications
Overload Capability
9.2.2 UPS Input
Table 9-3. UPS Input Rating
Operating Input Voltage
380/400/415 Vac
190/330–276/478V (-15%, +20%) at 100% load
Input Voltage Range
116/201-276/478V (-50%, +20%) at 50% load
Operating Input Frequency Range
50/60 Hz
Input Frequency Range
40-72Hz
See Table 3-5.
Operating Input Current
Adjustable
Input Current Harmonic Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
Battery Voltage
432 Vdc Internal
Battery Charging Capacity (432 Vdc)
5.3A maximum at any load up to100% load for 10 kVA UPS
5.3A maximum at any load up to100% load for 15 kVA UPS
5.3 A maximum at any load up to100% load for 20 kVA UPS
8A maximum at any load up to100% load for 30 kVA UPS
10.6A maximum at any load up to100% load for 40 kVA UPS
9.2.3 UPS Output
Table 9-4. UPS Output Rating
UPS Output Capacity
100% rated current
Output Voltage Regulation
± 1% (10% to 100% load)
Nominal Output Voltage
380 Vac, 400 Vac and 415 Vac nominal
2% maximum THD (linear load)
Output Voltage Harmonic Content
5% maximum THD (nonlinear load)
Output Current
See Table 3-5.
Output Voltage Balance
< 2% for 100% maximum load imbalance (linear load)
Output Voltage Phase Displacement
< 2.5° for 100% maximum load imbalance (linear load)
Frequency Regulation
0.1 Hz free running
Synchronous to Bypass
± 4 Hz (default setting)
Frequency Slew Rate
3 Hz per second (default setting)
Load Compatibility
0.9 PF Leading
0.7 PF Lagging
≦
110% for 60
minutes
≦
125% for 10
minutes
≦
150 % for 1 minutes
≧
150% for 500 milliseconds
82
Eaton 93E
MK2
UPS (10-40kVA, 380/400/415V) Installation and Operation
Summary of Contents for 93E MK2
Page 1: ...Eaton 93E MK2 UPS 10 40 kVA 380 400 415V Installation and Operation Manual...
Page 2: ......
Page 4: ......
Page 8: ......
Page 49: ...Notes 39 Eaton 93E MK2 UPS 10 40kVA 380 400 415V Installation and Operation...
Page 94: ......
Page 95: ......
Page 96: ...614 00389 00...