INSTALLATION
Eaton 9390 UPS, 9395 UPS, and 9395 SSBM Sync Control Installation and Operation Manual
S
P-164000052 Rev 2
3-20
TB1
TB2
15
16
1
2
Bld-Alarm-1-Rtn
Bld-Alarm-1
Bld-Alarm-2-Rtn
Bld-Alarm-2
Bld-Alarm-3-Rtn
Bld-Alarm-3
Bld-Alarm-4-Rtn
Bld-Alarm-4
Bld-Alarm-5
Bld-Alarm-5-Rtn
Bld-Alarm-6
Bld-Alarm-6-Rtn
Not Used
Alarm-Rly-NC
Alarm-Rly-NO
Alarm-Rly-Com
Figure 3‐17. Terminal Block TB2 Connector Assignments
NOTE
All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either
normally-open or normally-closed contacts. All control wiring and relay and switch contacts are customer‐supplied.
NOTE
The building alarms can be programmed to display the alarm functional name.
1
13
TB3
Out Volt C
Out Volt B
Out Volt A
CBP Out C
CBP Out B
CBP Out A
CBP In C
CBP In B
CBP In A
CBP In N
CBP Out N
Figure 3‐18. Terminal Block TB3 Connector Assignments