Eaton 9390 UPS, 9395 UPS, and 9395 SSBM Sync Control Installation and Operation Manual
S
P-164000052 Rev 2
3-1
Chapter 3
Installation
W
A
R
N
I
N
G
S
Only qualified service personnel (such as a licensed electrician) shall perform the electrical installation. Risk
of electrical shock.
S
Shut down all sources of power to the Eaton 9390 UPS or Eaton 9395 UPS or SSBM system before
connecting the control wiring to the Eaton Sync Control enclosure and UPS. Hazardous voltages exist inside
the UPS or SSBM and in the Eaton Sync Control enclosure. Check all terminal conductors with a known
serviceable voltmeter before connecting the wiring.
Once the Eaton Sync Control has been moved to its installed location, unpacked, and
inspected, it is ready for installation and wiring.
Use the applicable procedure from the following list to install the Eaton Sync Control
to the UPS:
S
With an Eaton 9390 UPS, proceed to paragraph 3.1.
S
With an Eaton 9395 UPS, proceed to paragraph 3.2.
S
With an Eaton 9395 SSBM, proceed to paragraph 3.3.
3.1
Installation and Wiring with an Eaton 9390 UPS
NOTE
When installing wiring connections, conduit must be installed between the Eaton Sync Control and the
UPS cabinet.
To install and wire:
1.
Install the Eaton Sync Control panel to the selected mounting location.
See Figure 2‐1 on page 2-2 for mounting hole dimensions and Figure 2‐2 on
page 2-3 for conduit entrance locations.
2.
Unfasten the front door latches and swing the door open.
3.
Complete all control wiring interconnections using Table 3‐1 for wiring
requirements.
Figure 3‐1 shows the Eaton Sync Control TB1 terminal block and ground terminal
locations. Figure 3‐2 shows the TB1 terminal block wiring detail.
Figure 3‐3 and Figure 3‐4 show the typical locations of the UPS TB1, TB2, and
TB6 interconnect terminal blocks. Figure 3‐5 shows the TB6 detail.
Refer to the applicable Eaton 9390 UPS Installation and Operation Manual listed
in paragraph 1.3 for UPS cabinet terminal locations and assignments, termination
requirements, conduit landing locations, and terminal access instructions.
4.
Verify the jumper is installed between Sync Control terminal TB1-40 and TB1-41
(see Figure 3‐2).
5.
When all wiring is complete, close the door and secure the latches.
Figure