OPERATING INSTRUCTIONS

Eaton 9390 UPS, 9395 UPS, and 9395 SSBM Sync Control Installation and Operation Manual  

S

  P-164000052 Rev 2

 www.eaton.com/powerquality

4-5

4.

Press the LOAD SYNC ENABLE pushbutton to enable the automatic
synchronization control. The pushbutton illuminates when the synchronization
control is enabled.

NOTE  

If both systems are operating normally, the ACTIVE MASTER SOURCE green indicator illuminates for the

selected master synchronization source.

NOTE  

If one system is in bypass, the ACTIVE MASTER SOURCE green indicator illuminates for the system in

bypass, regardless of the position of the PREFERRED SOURCE SELECTOR switch.

NOTE  

If one or both of the systems lose their bypass sources or if the bypass sources are no longer in

synchronization, the yellow SYNCHRONIZED TO LOAD indicator illuminates for the non-master system.

5.

To disable the automatic synchronization control, press the LOAD SYNC
ENABLE pushbutton and verify that the indicators, including the LOAD SYNC
ENABLE pushbutton, are off.

4.4

Maintenance Operations

Maintenance should be scheduled on a periodic basis, recommended not to exceed
one year. More frequent intervals are recommended if the equipment Is subjected to
highly repetitive operations.

D

 

A

 

N

 

G

 

E

 

R

This UPS contains 

LETHAL VOLTAGES

. All repairs and service should be performed by 

AUTHORIZED

SERVICE PERSONNEL ONLY

. There are 

NO USER SERVICEABLE PARTS

 inside the UPS.

Periodic inspections of the Eaton Sync Control should be made to determine if
components, wiring, and connections exhibit evidence of overheating or damage.

C

 

A

 

U

 

T

 

I

 

O

 

N

Refer to the maintenance  chapter in the applicable Eaton 9390 UPS,  Eaton 9395

 

UPS or 9395 SSBM Installation

and Operation Manual listed in paragraph 1.3 before beginning maintenance or repairs.

Summary of Contents for 9395 SSBM

Page 1: ...Eaton 9390 UPS 9395 UPS and 9395 SSBM Sync Control Installation and Operation Manual Sync Control Installation and Operation Manual...

Page 2: ......

Page 3: ...Eaton 9390 UPS 9395 UPS and 9395 SSBM Sync Control Installation and Operation Manual Sync Control Installation and Operation Manual...

Page 4: ...et de maintenance des batteries et de l onduleur Veuillez consulter enti rement ces instructions avant de faire fonctionner l quipement et conserver ce manuel afin de pouvoir vous y reporter ult rieur...

Page 5: ...ng the Site 2 1 2 2 1 Environmental and Installation Considerations 2 1 2 2 2 Eaton Sync Control Wiring Preparation 2 4 2 3 Inspecting and Unpacking the Eaton Sync Control 2 4 3 Installation 3 1 3 1 I...

Page 6: ...rol 3 10 Figure 3 8 Eaton 9395 UPS and Plus 1 UPS 450 550 kVA Interface Locations for Eaton Sync Control 3 11 Figure 3 9 Eaton 9395 UPS and Plus 1 UPS 650 825 kVA Interface Locations for Eaton Sync Co...

Page 7: ...transfer of the load from one load bus to another by means of downstream dual source solid state transfer switches Without the load sync option the two system output critical load buses could become o...

Page 8: ...a command or option that you type or enter at a prompt S Italic type highlights notes and new terms where they are defined S Screen type represents information that appears on the screen or LCD Icon D...

Page 9: ...inside the UPS or SBM WARNING S The UPS system contains its own energy source batteries The output terminals may carry live voltage even when the UPS is disconnected from an AC source S To reduce the...

Page 10: ...scribe S UPS or SBM cabinet optional components and accessory installation instructions including site preparation planning for installation and wiring and safety information Detailed illustrations of...

Page 11: ...offered as part of the sales contract for the UPS Contact service in advance usually a two week notice is required to reserve a preferred startup date 2 2 Preparing the Site For the Eaton Sync Contro...

Page 12: ...ol Installation and Operation Manual S P 164000052 Rev 2 www eaton com powerquality 2 2 FRONT VIEW 66 27 26 09 Dimensions are in millimeters inches 61 18 24 09 Four Mounting Holes in Rear of Panel 3 1...

Page 13: ...rol Installation and Operation Manual S P 164000052 Rev 2 www eaton com powerquality 2 3 LEFT SIDE VIEW RIGHT SIDE VIEW Knockout Holes for 1 Inch Conduit Dimensions are in millimeters inches 20 32 8 0...

Page 14: ...m 30 to 600V The wire should be rated at 600V 1A minimum and 12 AWG maximum S Sync Control dry contacts are rated at 250 Vac Vdc at 6A per contact maximum load S When installing external wiring betwee...

Page 15: ...1 Installation and Wiring with an Eaton 9390 UPS NOTE When installing wiring connections conduit must be installed between the Eaton Sync Control and the UPS cabinet To install and wire 1 Install the...

Page 16: ...e from another model UPS to an Eaton 9390 UPS using the Eaton Sync Control accessory use Phase A Phase B and Neutral connections from the other UPS DO NOT connect the other model UPS Phase C bypass an...

Page 17: ...ss NO OR J2 5 Industrial Relay Card TB1 1 On Bypass Common 14 AWG Twist Together J2 6 Industrial Relay Card TB1 2 On Bypass NO From UPS System B To Sync Control Function Note TB6 1 TB1 10 Bypass Volta...

Page 18: ...ut Voltage Phase A UPS System A Output Voltage Phase B UPS System A Output Voltage Neutral or Phase C for SBM UPS System B Output Voltage Phase A UPS System B Output Voltage Phase B UPS System B Outpu...

Page 19: ...9395 UPS and 9395 SSBM Sync Control Installation and Operation Manual S P 164000052 Rev 2 3 5 TB1 TB2 TB6 Mini CSB Building Alarm Terminal Block P5 Figure 3 3 Eaton 9390 UPS 40 80 kVA Interface Locat...

Page 20: ...9395 UPS and 9395 SSBM Sync Control Installation and Operation Manual S P 164000052 Rev 2 3 6 TB6 TB1 TB2 Mini CSB Building Alarm Terminal Block P5 Figure 3 4 Eaton 9390 UPS 100 160 kVA Interface Loca...

Page 21: ...Bypass Voltage Phase B Output Voltage Phase A Output Voltage Phase B Output Voltage Neutral Bypass Voltage Return Phase B TB6 Figure 3 5 TB6 Terminal Block Detail 1 8 P5 BUILDING ALARM 3 BUILDING ALA...

Page 22: ...locations and assignments termination requirements conduit landing locations and terminal access instructions NOTE Completethe wiring to the X Slot Relay Interface Card or Industrial Relay Card termin...

Page 23: ...ss NO OR J2 5 Industrial Relay Card TB1 1 On Bypass Common 14 AWG Twist Together J2 6 Industrial Relay Card TB1 2 On Bypass NO From UPS System B To Sync Control Function Note TB6 1 TB1 10 Bypass Volta...

Page 24: ...164000052 Rev 2 3 10 TB3 TB6 NOTE Interface connections are located in the same positions on the 9395 550 275 UPS 225 550 kVA and the 9395 UPS 300 kVA X Slot Communication Bays Install Relay Interface...

Page 25: ...S P 164000052 Rev 2 3 11 TB3 TB6 NOTE Interface connections are located in the same positions on the 9395 Plus 1 UPS 225 275 kVA X Slot Communication Bays Install Relay Interface Card in any open bay...

Page 26: ...Control Installation and Operation Manual S P 164000052 Rev 2 3 12 TB3 TB6 X Slot Communication Bays Install Relay Interface Card in any open bay ISBM SECTION Figure 3 9 Eaton 9395 UPS and Plus 1 UPS...

Page 27: ...M Sync Control Installation and Operation Manual S P 164000052 Rev 2 3 13 TB3 TB6 X Slot Communication Bays Install Relay Interface Card in any open bay ISBM SECTION Figure 3 10 Eaton 9395 UPS 1000 11...

Page 28: ...llation and Operation Manual S P 164000052 Rev 2 3 14 Strain Relief Bushing Figure 3 11 Relay Interface Card End View 1 15 K4 Normally Open On Bypass 6 4 K4 Common On Bypass Strain Relief Bushing 5 K4...

Page 29: ...lock J2 from Relay Contacts to Customer s Monitoring Equipment Figure 3 13 Industrial Relay Card Table 3 3 IRC Wire Terminations IRC Terminal Function Remarks J2 1 NC Normal Mode J2 2 COM J2 3 NO J2 4...

Page 30: ...for wiring requirements Figure 3 1 shows the Eaton Sync Control TB1 terminal block and ground terminal locations Figure 3 2 shows the TB1 terminal block wiring detail Figure 3 14 shows the typical lo...

Page 31: ...7 Sync Control Trouble Return 24 Vdc Optional TB4 7 TB1 1 On Bypass Common 14 AWG Twist Together TB4 8 TB1 2 On Bypass NO From SSBM B To Sync Control Function Note TB3 6 TB1 10 Bypass Voltage Phase A...

Page 32: ...Control Installation and Operation Manual S P 164000052 Rev 2 3 18 X Slot Communication Bays TB1 and TB2 See Figure 3 15 for detail TB4 TB5 TB6 and TB7 TB3 See Figure 3 18 for terminal assignments Fi...

Page 33: ...M Sync Control Installation and Operation Manual S P 164000052 Rev 2 3 19 TB1 TB2 See Figure 3 17 for terminal assignments Figure 3 15 TB1 and TB2 Interface Terminal Detail TB4 TB5 TB6 TB7 On Bypass F...

Page 34: ...All building alarm inputs require an isolated normally open or normally closed contact or switch rated at 24 Vdc 20 mA minimum connected between the alarm input and common terminal as shown Building...

Page 35: ...95 SBM to UPS Interconnection System Control Wiring From SSBM To UPS 1 Function Note TB3 9 TB6 1 Bypass Voltage Phase B 480 Vac 14 AWG Twist Together From UPS 1 To UPS 2 Function Note TB6 1 TB6 1 Bypa...

Page 36: ...INSTALLATION Eaton 9390 UPS 9395 UPS and 9395 SSBM Sync Control Installation and Operation Manual S P 164000052 Rev 2 3 22 This page intentionally left blank...

Page 37: ...onization reference to each system Each system uses this reference to regulate the inverter phase relationship so that the two system outputs can maintain synchronization with each other To establish...

Page 38: ...egardless of the position of the PREFERRED SOURCE SELECTOR switch S Dual redundant logic power supplies are incorporated within the Eaton Sync Control ensuring both systems remain synchronized even du...

Page 39: ...n the non master system mode NOTE At any given time only one of the UPS systems can be in the non master system mode Figure 4 2 Synchronization Reference Control 4 3 Operation Perform the following pr...

Page 40: ...cates UPS System A is the active master source This indicator may illuminate even if the PREFERRED SOURCE SELECTOR switch is not set to the corresponding position 4 UPS SYSTEM A SYNCHRONIZED TO LOAD B...

Page 41: ...ONIZED TO LOAD indicator illuminates for the non master system 5 To disable the automatic synchronization control press the LOAD SYNC ENABLE pushbutton and verify that the indicators including the LOA...

Page 42: ...OPERATING INSTRUCTIONS Eaton 9390 UPS 9395 UPS and 9395 SSBM Sync Control Installation and Operation Manual S P 164000052 Rev 2 www eaton com powerquality 4 6 This page intentionally left blank...

Page 43: ...erforms startup and commissioning of the Product b if the Product is moved to a new location by someone other than an authorized Eaton Customer Service Engineer in the USA or Agent outside of the USA...

Page 44: ...WARRANTY Eaton 9390 UPS 9395 UPS and 9395 SSBM Sync Control Installation and Operation Manual S P 164000052 Rev 2 www eaton com powerquality 5 2 This page intentionally left blank...

Page 45: ......

Page 46: ...P 1640000522 P 164000052 2...

Reviews: