83
InsTALLATIon And oPerATIon MAnuAL
25-16330-B December 2019 www.eaton.com
Appendix
Detector Base Wiring
Supply Voltage
18 - 30V DC
Cable Size
0 .5 - 2 .5mm²
Recommended cable types
FIRETUF, FP200 or MICC
Mounting Hole Centres
50 - 80mm
Wiring Hints
1. Each terminal is suitable for clamping up to 2 wires
2. Clamping of 2 wires of very different diameters under one screw
is not recommended.
3. Suitable for mounting to mounting boxes with 50-80mm fixing centres.
General
If difficulty is experienced when mounting the sensor, this may be due
to the following:
1. Wiring causing an obstruction - move or shorten wires.
2. Although the base is tolerant to uneven mounting surfaces, a very uneven
surface may cause the base to deform when the mounting screws are
tightened down - loosen screws to reduce this or slide base to a
flat position.
WArnInG
do noT use HIGH VoLTAGe TesTers WHen sensors or ConTroL PAneL Are
ConneCTed To THe sYsTeM
Figure 50 . Wiring diagram for sensor Base