37
InsTALLATIon And oPerATIon MAnuAL
25-16330-B December 2019 www.eaton.com
Commissioning the panel
Figure 7 . Panel outputs
Dependency detection
Each panel output can be assigned a unique list of zones derived from the zones
available on the loop, to activate this output, two unique zones from this list have to
be in fire or alternatively any zone outside this list will trigger the output also .
When the ‘Dependency’ box is checked - the ‘Allocate device’ button allows the user
to populate this list .