23
InsTALLATIon And oPerATIon MAnuAL
25-16330-B December 2019 www.eaton.com
System Overview
Technical Specification
Power supply (Approved en54 pt 4)
Mains
Nominal Voltage
230V AC + 10%, -15%
Nominal Current
40mA
Maximum Current
500mA
Input Fuse R1
Anti Surge 1.6A
Output Voltage including tolerances
26V
= 25 to 28.6V
26V RAW
= 20.4 to 29.0V
5V Output
= 4.85V to 5.15V
Ripple Voltages
26V
= 800mV
26V RAW
= 800mV
5V Output
= 430mV
Maximum Loadings
26V O/P
= 0.48A *I max b
26V RAW O/P
= 1.2A *I max b
5V
= 0.5A
Standby Current
(2 Loops Loaded)
26V
= 140mA *I max a
26V RAW
= 50mA *I max a
26V
= 140mA *I min
26V RAW
= 50mA *I min
5V
= 80mA
* I max a, I max b & I min = Current as specified in BS EN54-4 Published 2006 (Amendments 1 & 2)
Please refer to local standards for details of the maximum allowable area to be
covered by a single spur .
Integral Power Supply and Battery
The panel is designed for ease of installation, the power supply and battery are
integral to the main control panel so only a single panel is required .