97
InsTALLATIon And oPerATIon MAnuAL
25-16330-B December 2019 www.eaton.com
Appendix
Micro Input Module Wiring
To install the device
1.
Fit the box in position using the mounting details below .
2.
Connect the unit according to the diagram .
3.
Recommended Cable Type: FIRETUF, FP200, MICC .
ote:
n
No addressing of the interface is required . See control panel operation for
details . There are no serviceable parts so no maintenance procedures apply .
Figure 64 . standard connections
1.
Only connect cable screen to its adjacent earth terminal .
2.
The end of line resistor provided must always be fitted, even if the
input is unused .
3.
Monitored inputs can detect open or short circuit faults .
Battery Disposal Instructions
Although batteries contain lead and small amounts of antimony and arsenic, they are
safe if handled according to the accompanying guide . The battery cells must not be
dismantled as this involves several hazards, which are best handled under controlled
conditions, using specialised equipment . No attempt should be made to repair any
batteries; they should be treated as disposable when they have outlived their use .
Batteries must be disposed of in accordance with current waste disposal and
pollution legislation and in particular; The Environment Protection Act 1990, Special
Waste Regulation 1996 . It is recommended that the following authorities are
contacted before any attempt is made to dispose of batteries; Environment Agency
Local office, Local Authority Environmental Health or Waste Handling department .