background image

16

Instruction Book 

IB02707112E

August 2015

50/75VCPW-VSR

Breaker To Vacuum Starter Replacement Unit

EATON CORPORATION www.eaton.com

SECTION 5: INSPECTION, MAINTENANCE, 
AND INSTALLATION

 WARNING

ALL WORK PERFORMED ON THIS STARTER SHOULD BE DONE WITH THE 

MAIN DISCONNECT DEVICE OPEN AND LOCKED OUT. AS WITH ANY 

STARTER OF THIS VOLTAGE, THERE IS DANGER OF ELECTROCUTION AND/

OR SEVERE BURNS. MAKE CERTAIN THAT POWER IS OFF. CHECK FOR 

VOLTAGE WITH VOLTAGE SENSOR OR A METER OF THE APPROPRIATE 

RANGE. MAKE CERTAIN THAT ALL TRANSFORMERS ARE ISOLATED 

TO PREVENT FEEDBACK AND THE RESULTANT GENERATION OF HIGH 

VOLTAGE.

The starter should be serviced on a regular basis. The time interval 

between maintenance checks is variable and dependant on factors 

such as environment, duty cycle, etc. Unless the experience of the 

maintenance personnel suggests a different service interval, the 

contactor should go through a checkout after each 50,000 operations 

or annually, which ever occurs first.

5.1  GENERAL

The starter should be kept clean and free from dust and other 

accumulated deposits. Dust can be removed from the starter by 

wiping with a lint free cloth.
Inspect for loose joints that produce excess heat and discolor 

conductors. Verify that insulation has not been damaged by high 

temperatures. Do not over-torque bolts while verifying tightness. 

Hardware is both Metric and US standard sizes. Refer to Table 5.3 

for recommended torque values.

 WARNING

BEFORE PLACING THE STARTER IN SERVICE, CAREFULLY FOLLOW THE 

INSTALLATION PROCEDURE IN THIS MANUAL AND THE SAFE PRACTICES 

SET FORTH IN SECTION 2. NOT FOLLOWING THE PROCEDURE MAY RESULT 

IN INCORRECT STARTER OPERATION LEADING TO DEATH, BODILY INJURY, 

AND PROPERTY DAMAGE.

When the starter is first commissioned into service and each time 

the starter is returned to service, it should be carefully examined and 

checked to make sure it is clean and operating correctly.

5.2  EXAMINATION FOR DAMAGE

Examine the starter for loose or obviously damaged parts. Never 

attempt to install nor operate a damaged starter.

5.2.1  NAMEPLATE VERIFICATION

Compare the starter nameplate information with switchgear 

drawings for compatibility. Starter and compartment code plates do 

match power ratings, but do not match control voltages.

5.3  INITIAL INSPECTION AND OPERATION

Inspect the starter for any damage that occurred during shipment, 

storage, and installation.
Set the dip switches in the coil control board for the proper control 

voltage and dropout time (Figures 4.1 and 4.2 and Tables 5.1 and 

5.2). When control information is supplied, dip switches will be 

factory set.
Sequence the control circuit, including closing the starter with the 

main power circuits de-energized and locked out.
Verify that the starter will be connected to an incoming power 

supply and outgoing load with characteristics agreeing with the 

starter rating and coil burden requirements.

1 2  3  4  5  6

ON

OFF

Dip Switch

Figurt 5.1. CNil CNnorNl BNard wioh Dip Swioch

Figurt 5.2. CNil CNnorNl BNard RtmNval

Tablt 5.1.  Dip Swioch Stooing-CNnorNl VNloagt

Setting

SW1

SW2

SW3

110 vAC 50 Hz

Off

Off

Off

120 vAC 60 Hz

On

Off

Off

220 vAC 50 Hz

Off

On

Off

240 vAC 60 Hz

Off

On

Off

125 vDC

Off

Off

On

Tablt 5.2.  CNnorNl BNard DrNpNuo Stooings

Delay Setting

SW4

SW5

SW6

30 ms

Off

Off

Off

50 ms

On

Off

Off

130 ms

Off

On

Off

250 ms

On

On

Off

330 ms

Off

Off

On

Summary of Contents for 75VCPW-VSR

Page 1: ...August 2015 Instruction Book IB02707112E 50 75VCPW VSR Breaker To Vacuum Starter Replacement Unit 50VCPW VSR 350 390A Shown Supersedes May 2014 Effective...

Page 2: ...WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF E...

Page 3: ...AFETY CODES SAFETY STANDARDS AND OR REGULATIONS AS THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED TO THESE VACUUM STARTER REPLACEMENT UNITS ARE DESIGNED TO BE INSTALLED PURSUAN...

Page 4: ...ed as Cutler Hammer and or Eaton WARNING SATISFACTORY PERFORMANCE OF THESE UNITS ARE CONTINGENT UPON PROPER APPLICATION CORRECT INSTALLATION AND ADEQUATE MAINTENANCE THIS INSTRUCTION BOOK MUST BE CARE...

Page 5: ...Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H I J K 50VCPW VSR 250 230A 390A 29 44 29 12 10 00 29 81 12 00 13 63 27 80 29 56 2 25 20 88 24 63 50VCPW VSR 350 230A 390A 31 44 2...

Page 6: ...any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a unit with the secondary test coupler engaged Failure to d...

Page 7: ...ntact Wear Gauge Optional item used to check contact wear Style 5259C11H01 See Section 5 Racking Handle The original VCP W racking handle is used to assist in moving the MV VSR into and out of the cel...

Page 8: ...falling objects excessive moisture etc must be provided Containers should be arranged to permit free circulation of air on all sides and temporary heaters should be used to minimize condensation Mois...

Page 9: ...ement Unit EATON CORPORATION www eaton com Figure 3 3 Front External View of 50VCPW VSR Front External View 1 Lifting Point 4 Push To Open Button 7 Lift Pull Handle 2 Extension Rail Interlock 5 Main C...

Page 10: ...75VCPW VSR BreakerTo Vacuum Starter Replacement Unit EATON CORPORATION www eaton com Figure 3 4 Rear External View of 50VCPW VSR Rear External View 1 Fuse 3 Phase Barrier 5 Primary Disconnects 2 Lifti...

Page 11: ...losing circuit which remains made while the contactor is being racked between the Test and Connected positions Consequently it prevents the starter from closing automatically even though the control s...

Page 12: ...iliary Contacts 12 Optional Auxiliary Contacts 6 Coil Control Board Terminal Block 13 Stop Assembly 7 Axial Magnetic Coil 3 SL400 Only 14 Base Plate SL Back View Major Components 1 Rear Mounting Holes...

Page 13: ...be wired in parallel with the a contacts on the Electro MOC The original b contacts must be wired in series with the b contacts on the Electro MOC It is suggested that polarized voltages should not b...

Page 14: ...arters are made of glass polyester They are all easily removed for access to the fuses Table 4 2 Electro MOC Contact Ratings Contact Circuit Volts Short Time Rating Amps Continuous Rating Amps Interru...

Page 15: ...the racking device is to move the VSR between the TEST and CONNECTED positions For the VCPW VSR the device is a drive screw and drive nut Although the device is mounted in the switchgear compartment a...

Page 16: ...IN SECTION 2 NOT FOLLOWING THE PROCEDURE MAY RESULT IN INCORRECT STARTER OPERATION LEADING TO DEATH BODILY INJURY AND PROPERTY DAMAGE When the starter is first commissioned into service and each time...

Page 17: ...tage for one minute Repeat for the remaining phases Successful withstand indicates satisfactory insulation strength of the primary circuit Open the starter Connect the high potential lead of the test...

Page 18: ...BE INSERTED INTO THE INTENDED STRUCTURE WARNING ARC FLASH INCIDENCES WITH MV SWITCHGEAR CAN OCCUR DURING THE PROCESS OF INSERTING AND REMOVING VSR UNITS IN SWITCHGEAR CUBICLES IT IS STRONGLY RECOMMEND...

Page 19: ...with the structure mounted racking shaft Figure 5 9 Turn the racking in crank in a clockwise direction and the VSR will move slowly toward the rear of the structure When the VSR reaches the CONNECTED...

Page 20: ...8 Install the bolt securing the vacuum interrupter to the upper terminal do not tighten 9 Install bolt and shunt supports securing lower terminal to housing Figure 6 6 When tightening insure laminated...

Page 21: ...pplied the contactor should close cleanly When power is removed the moving armature should securely contact the stop assembly 6 3 Control Board Check and Replacement To verify the output of the contro...

Page 22: ...he coil has the proper resistance connect an ohmmeter across the coil leads where they are connected to the bridge rectifier Refer to Table 6 1 for the correct impedance for the different voltage coil...

Page 23: ...LLATION 1 Remove the existing roller bracket from the contactor moving armature if one is attached 2 Secure the new roller bracket and bearing assembly with two 6mm x 25mm bolts with lock washers and...

Page 24: ...ER TO CONTACTOR COIL IF VOLTAGE IS BACK FED INTO A TRANSFORMER HIGH VOLTAGE WILL BE GENERATED ON THE TRANSFORMER PRIMARY HIGH VOLTAGE CAN CAUSE SERIOUS INJURY OR DEATH 6 Apply force to latch assembly...

Page 25: ...clear barrier in place and can be lifted straight up for access to the fuse hardware Figure 7 1 2 To remove the side phase barrier for access to the outer fuse lift the phase barrier straight up and...

Page 26: ...Part Number Description 2147A58G02 Vacuum Interrupter Assembly for SL 160 200 320 400 2147A58G03 Coil Control Board 2147A58G04 Auxiliary Contact Kit 2NO 2NC 2147A58G05 Auxiliary Contact Kit 3NO 3NC fo...

Page 27: ...27 Instruction Book IB02707112E August 2015 50 75VCPW VSR BreakerTo Vacuum Starter Replacement Unit EATON CORPORATION www eaton com...

Page 28: ...or Avenue Cleveland OH 44114 USA Eaton com 2014 Eaton Corporation All Rights Reserved Printed in USA Publication No IB02707112E August 2015 Eaton is a registered trademark of Eaton Corporation All tra...

Reviews: