Instruction Book 

IB02707112E

August 2015

50/75VCPW-VSR

Breaker To Vacuum Starter Replacement Unit

EATON CORPORATION www.eaton.com

SECTION 3: RECEIVING, HANDLING, AND 
STORAGE

Type VCP-W VSR-series breaker to vacuum starter replacement units 

are subjected to complete factory production tests and inspection 

before being packed. They are shipped in packages designed to 

provide maximum protection to the equipment during shipment 

and storage and at the same time to provide convenient handling. 

Accessories such as the cell code plate, etc. are shipped with the 

unit (Figure 3.1).

3.1  RECEIVING

Until the unit is ready to be delivered to the switchgear site for 

installation, DO NOT remove it from the shipping crate. If the unit 

is to be placed in storage, maximum protection can be obtained by 

keeping it in its crate.
Upon receipt of the equipment, inspect the crates for any signs of 

damage or rough handling. Open the crates carefully to avoid any 

damage to the contents. Use a nail puller rather than a crow bar 

when required.
When opening the crates, be careful that any loose items or 

hardware are not discarded with the packing material. Check the 

contents of each package against the packing list.
Examine the unit for any signs of shipping damage such as broken, 

missing or loose hardware, damaged or deformed insulation and 

other components. File claims immediately with the carrier if 

damaged or loss is detected and notify the nearest Eaton’s Electrical 

Services & Systems office.

Tools and Accessories

CNnoaco Wtar  Gaugte: 

Optional item used to check contact wear. 

(Style 5259C11H01) (See Section 5)

Racking Handlte:

 The original VCP-W racking handle is used to assist 

in moving the MV-VSR into and out of the cell.

Lifoing YNkte: 

Optional lifting device that can be used to install a VSR 

into upper compartment of VCP-W switchgear. (Style 94M7103G99)

3.2  HANDLING

 WARNING

DO NOT USE ANY LIFTING DEVICE AS A PLATFORM FOR PERFORMING 

MAINTENANCE, REPAIR OR ADJUSTMENT OF THE UNIT OR FOR OPENING, 

CLOSING THE CONTACTS OR CHARGING THE SPRINGS. THE UNIT MAY 

SLIP OR FALL CAUSING SEVERE PERSONAL INJURY. ALWAYS PERFORM 

MAINTENANCE, REPAIR AND ADJUSTMENTS ON A WORKBENCH 

CAPABLE OF SUPPORTING THE UNIT. 

VCPW-VSR unit shipping containers are designed to be handled 

either by use of a rope sling and overhead lifting device or by a 

fork lift truck. If containers must be skidded for any distance, it is 

preferable to use roller conveyors or individual pipe rollers.

Once the unit has been inspected for shipping damage, it is best to 

return it to its original shipping crate until it is ready to be installed in 

the Metal-Clad Switchgear.

When the unit is ready for installation, a lifting harness in conjunction 

with an overhead lift or portable floor lift can be used to move the 

unit, if this is preferable to rolling the unit on the floor using self 

contained wheels. If the unit is to be lifted, position the lifting device 

(lifting straps should have at least a 1600 pound capacity) over the 

unit and insert the lifting harness hooks into the unit side openings 

and secure. Be sure the hooks are firmly attached before lifting 

the unit. Stand a safe distance away from the unit while lifting and 

moving.

Figurt 3.1. CNnoaco Wtar Gaugt

Summary of Contents for 75VCPW-VSR

Page 1: ...August 2015 Instruction Book IB02707112E 50 75VCPW VSR Breaker To Vacuum Starter Replacement Unit 50VCPW VSR 350 390A Shown Supersedes May 2014 Effective...

Page 2: ...WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF E...

Page 3: ...AFETY CODES SAFETY STANDARDS AND OR REGULATIONS AS THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED TO THESE VACUUM STARTER REPLACEMENT UNITS ARE DESIGNED TO BE INSTALLED PURSUAN...

Page 4: ...ed as Cutler Hammer and or Eaton WARNING SATISFACTORY PERFORMANCE OF THESE UNITS ARE CONTINGENT UPON PROPER APPLICATION CORRECT INSTALLATION AND ADEQUATE MAINTENANCE THIS INSTRUCTION BOOK MUST BE CARE...

Page 5: ...Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H I J K 50VCPW VSR 250 230A 390A 29 44 29 12 10 00 29 81 12 00 13 63 27 80 29 56 2 25 20 88 24 63 50VCPW VSR 350 230A 390A 31 44 2...

Page 6: ...any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a unit with the secondary test coupler engaged Failure to d...

Page 7: ...ntact Wear Gauge Optional item used to check contact wear Style 5259C11H01 See Section 5 Racking Handle The original VCP W racking handle is used to assist in moving the MV VSR into and out of the cel...

Page 8: ...falling objects excessive moisture etc must be provided Containers should be arranged to permit free circulation of air on all sides and temporary heaters should be used to minimize condensation Mois...

Page 9: ...ement Unit EATON CORPORATION www eaton com Figure 3 3 Front External View of 50VCPW VSR Front External View 1 Lifting Point 4 Push To Open Button 7 Lift Pull Handle 2 Extension Rail Interlock 5 Main C...

Page 10: ...75VCPW VSR BreakerTo Vacuum Starter Replacement Unit EATON CORPORATION www eaton com Figure 3 4 Rear External View of 50VCPW VSR Rear External View 1 Fuse 3 Phase Barrier 5 Primary Disconnects 2 Lifti...

Page 11: ...losing circuit which remains made while the contactor is being racked between the Test and Connected positions Consequently it prevents the starter from closing automatically even though the control s...

Page 12: ...iliary Contacts 12 Optional Auxiliary Contacts 6 Coil Control Board Terminal Block 13 Stop Assembly 7 Axial Magnetic Coil 3 SL400 Only 14 Base Plate SL Back View Major Components 1 Rear Mounting Holes...

Page 13: ...be wired in parallel with the a contacts on the Electro MOC The original b contacts must be wired in series with the b contacts on the Electro MOC It is suggested that polarized voltages should not b...

Page 14: ...arters are made of glass polyester They are all easily removed for access to the fuses Table 4 2 Electro MOC Contact Ratings Contact Circuit Volts Short Time Rating Amps Continuous Rating Amps Interru...

Page 15: ...the racking device is to move the VSR between the TEST and CONNECTED positions For the VCPW VSR the device is a drive screw and drive nut Although the device is mounted in the switchgear compartment a...

Page 16: ...IN SECTION 2 NOT FOLLOWING THE PROCEDURE MAY RESULT IN INCORRECT STARTER OPERATION LEADING TO DEATH BODILY INJURY AND PROPERTY DAMAGE When the starter is first commissioned into service and each time...

Page 17: ...tage for one minute Repeat for the remaining phases Successful withstand indicates satisfactory insulation strength of the primary circuit Open the starter Connect the high potential lead of the test...

Page 18: ...BE INSERTED INTO THE INTENDED STRUCTURE WARNING ARC FLASH INCIDENCES WITH MV SWITCHGEAR CAN OCCUR DURING THE PROCESS OF INSERTING AND REMOVING VSR UNITS IN SWITCHGEAR CUBICLES IT IS STRONGLY RECOMMEND...

Page 19: ...with the structure mounted racking shaft Figure 5 9 Turn the racking in crank in a clockwise direction and the VSR will move slowly toward the rear of the structure When the VSR reaches the CONNECTED...

Page 20: ...8 Install the bolt securing the vacuum interrupter to the upper terminal do not tighten 9 Install bolt and shunt supports securing lower terminal to housing Figure 6 6 When tightening insure laminated...

Page 21: ...pplied the contactor should close cleanly When power is removed the moving armature should securely contact the stop assembly 6 3 Control Board Check and Replacement To verify the output of the contro...

Page 22: ...he coil has the proper resistance connect an ohmmeter across the coil leads where they are connected to the bridge rectifier Refer to Table 6 1 for the correct impedance for the different voltage coil...

Page 23: ...LLATION 1 Remove the existing roller bracket from the contactor moving armature if one is attached 2 Secure the new roller bracket and bearing assembly with two 6mm x 25mm bolts with lock washers and...

Page 24: ...ER TO CONTACTOR COIL IF VOLTAGE IS BACK FED INTO A TRANSFORMER HIGH VOLTAGE WILL BE GENERATED ON THE TRANSFORMER PRIMARY HIGH VOLTAGE CAN CAUSE SERIOUS INJURY OR DEATH 6 Apply force to latch assembly...

Page 25: ...clear barrier in place and can be lifted straight up for access to the fuse hardware Figure 7 1 2 To remove the side phase barrier for access to the outer fuse lift the phase barrier straight up and...

Page 26: ...Part Number Description 2147A58G02 Vacuum Interrupter Assembly for SL 160 200 320 400 2147A58G03 Coil Control Board 2147A58G04 Auxiliary Contact Kit 2NO 2NC 2147A58G05 Auxiliary Contact Kit 3NO 3NC fo...

Page 27: ...27 Instruction Book IB02707112E August 2015 50 75VCPW VSR BreakerTo Vacuum Starter Replacement Unit EATON CORPORATION www eaton com...

Page 28: ...or Avenue Cleveland OH 44114 USA Eaton com 2014 Eaton Corporation All Rights Reserved Printed in USA Publication No IB02707112E August 2015 Eaton is a registered trademark of Eaton Corporation All tra...

Reviews: