Instruction Book 

IB02707112E

August 2015

50/75VCPW-VSR

Breaker To Vacuum Starter Replacement Unit

EATON CORPORATION www.eaton.com

procedures are similar. If it is necessary to reference anything in the 

unit compartment, refer to the original instruction books supplied 

with the assembly.
Refer to Figures 3.3 and 3.4, for any parts identification required 

during these installation procedures.
a.  The starters faceplate and barriers must be positioned properly 

and securely bolted in position, as shown in Figures 3.3 and 3.4, 

before inserting the starter into the cell.
b.  Carefully follow the insertion procedure in section 5 to get 

the VSR unit into the test position inside the compartment and 

to engage the secondary contacts to proceed with the electrical 

operations check.

 WARNING

AS SOON AS THE SECONDARY CONTACTS MATE UP, THE STARTER IS 

READY FOR OPERATION IF THE CONTROL CIRCUIT IS ENERGIZED.

c.  Once the starter is in the test position, it may be electrically 

closed and tripped by using a control switch on the cell door, or it 

may be manually tripped by means of the trip button, located on the 

faceplate of the starter.

5.9 CELL CODE / REJECTION PLATE INSTALLATION

Cell code plates and circuit breaker rejection plates are required to 

reject circuit breakers and breaker to vacuum starter replacement 

units that do not match the electrical rating structure of the existing 

cell. If the momentary rating of a unit is increased, a code plate and 

a cell rejection plate must be installed to accept the new unit and 

reject all others of lesser ratings. If momentary ratings of the new 

unit is the same as the original breaker, then the original cell code 

plate may be retained. 
A unit code plate is factory installed on VSR-series units. Cell code 

plates are automatically furnished with each unit. (Rejection plates 

have stamped orientation as “LH” and “RH” for clarity.) (Figure 5.5)

 NOTICE

REJECTION PLATES MUST BE INSTALLED INTO THE PROPER INTENDED 

SWITCHGEAR PER THE NAMEPLATE RATING. IF THE REJECTION PLATE IS 

NOT INSTALLED CORRECTLY THE VSR CAN NOT BE INSERTED INTO THE 

INTENDED STRUCTURE.

 WARNING

ARC FLASH INCIDENCES WITH MV SWITCHGEAR CAN OCCUR DURING THE 

PROCESS OF INSERTING AND REMOVING VSR UNITS IN SWITCHGEAR 

CUBICLES. IT IS STRONGLY RECOMMENDED THAT PROPER PPE 

(PERSONAL PROTECTIVE EQUIPMENT) BE WORN BY PERSONNEL WHO 

RACK UNITS USING THE MANUAL RACKING HANDLE OR THE ROTARY 

RACKING HANDLE. EATON CORPORATION PROVIDES A UNIVERSAL 

REMOTE POWER RACKING SYSTEM (RPR-2) WHICH IS COMPATIBLE WITH 

THE INTERNAL ROTARY RACKING UNITS. THIS SYSTEM MAY ALLOW 

PERSONNEL TO WEAR A LOWER LEVEL OF PPE DURING THE INSERTION 

OR REMOVAL PROCESS AS LONG AS RACKING CAN BE PERFORMED FROM 

OUTSIDE THE FLASH PROTECTION BOUNDARY. 

5.10 INSERTION PROCEDURE

 WARNING

EXAMINE THE INSIDE OF THE CELL BEFORE INSERTING THE STARTER 

FOR EXCESSIVE DIRT OR ANYTHING THAT MIGHT INTERFERE WITH THE 

STARTER TRAVEL.

KEEP HANDS OFF THE TOP EDGE OF THE FRONT BARRIER WHEN PUSHING 

A STARTER INTO A CELL. FAILURE TO DO SO COULD RESULT IN BODILY 

INJURY, IF FINGERS BECOME WEDGED BETWEEN THE STARTER AND 

THE CELL. USE BOTH FULLY OPENED HANDS FLAT ON THE FRONT OF THE 

STARTER TO ADVANCE INO THE STRUCTURE.

If the VCPW-VSR is being inserted into an upper compartment or 

will be positioned in a lower compartment without the use of a 

drawout ramp or dockable dolly, the extension rails must first be 

put in position. Carefully engage the left and right extension rails to 

the fixed structure rails and ensure they are properly seated in place 

(Figure 5.6). Once the extension rails are properly in place, the VSR 

can be carefully loaded on the extension rails using an overhead lifter 

and lifting yoke. Remove the lifting yoke when the VSR is securely 

seated on the extension rails.
Push the VSR into the compartment until the TEST position is 

reached as confirmed by a metallic sound of the racking latch 

engaging the racking nut (Figures 5.7). Once the VSR is in the TEST 

position, the extension rails can be removed.
To engage the secondary contacts, raise the handle to the 

secondary disconnect cage and pull the cage forward as far as 

possible (Figure 5.8). As soon as control power is available, the 

motor will start charging the closing springs. 

Figurt 5.5. VCPW-VSR RtjtcoiNn Plaot (230A VSR ShNwn)

Figurt 5.4. VCPW-VSR CNdt Plaot (250MVA VSR ShNwn)

Summary of Contents for 75VCPW-VSR

Page 1: ...August 2015 Instruction Book IB02707112E 50 75VCPW VSR Breaker To Vacuum Starter Replacement Unit 50VCPW VSR 350 390A Shown Supersedes May 2014 Effective...

Page 2: ...WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF E...

Page 3: ...AFETY CODES SAFETY STANDARDS AND OR REGULATIONS AS THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED TO THESE VACUUM STARTER REPLACEMENT UNITS ARE DESIGNED TO BE INSTALLED PURSUAN...

Page 4: ...ed as Cutler Hammer and or Eaton WARNING SATISFACTORY PERFORMANCE OF THESE UNITS ARE CONTINGENT UPON PROPER APPLICATION CORRECT INSTALLATION AND ADEQUATE MAINTENANCE THIS INSTRUCTION BOOK MUST BE CARE...

Page 5: ...Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H I J K 50VCPW VSR 250 230A 390A 29 44 29 12 10 00 29 81 12 00 13 63 27 80 29 56 2 25 20 88 24 63 50VCPW VSR 350 230A 390A 31 44 2...

Page 6: ...any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a unit with the secondary test coupler engaged Failure to d...

Page 7: ...ntact Wear Gauge Optional item used to check contact wear Style 5259C11H01 See Section 5 Racking Handle The original VCP W racking handle is used to assist in moving the MV VSR into and out of the cel...

Page 8: ...falling objects excessive moisture etc must be provided Containers should be arranged to permit free circulation of air on all sides and temporary heaters should be used to minimize condensation Mois...

Page 9: ...ement Unit EATON CORPORATION www eaton com Figure 3 3 Front External View of 50VCPW VSR Front External View 1 Lifting Point 4 Push To Open Button 7 Lift Pull Handle 2 Extension Rail Interlock 5 Main C...

Page 10: ...75VCPW VSR BreakerTo Vacuum Starter Replacement Unit EATON CORPORATION www eaton com Figure 3 4 Rear External View of 50VCPW VSR Rear External View 1 Fuse 3 Phase Barrier 5 Primary Disconnects 2 Lifti...

Page 11: ...losing circuit which remains made while the contactor is being racked between the Test and Connected positions Consequently it prevents the starter from closing automatically even though the control s...

Page 12: ...iliary Contacts 12 Optional Auxiliary Contacts 6 Coil Control Board Terminal Block 13 Stop Assembly 7 Axial Magnetic Coil 3 SL400 Only 14 Base Plate SL Back View Major Components 1 Rear Mounting Holes...

Page 13: ...be wired in parallel with the a contacts on the Electro MOC The original b contacts must be wired in series with the b contacts on the Electro MOC It is suggested that polarized voltages should not b...

Page 14: ...arters are made of glass polyester They are all easily removed for access to the fuses Table 4 2 Electro MOC Contact Ratings Contact Circuit Volts Short Time Rating Amps Continuous Rating Amps Interru...

Page 15: ...the racking device is to move the VSR between the TEST and CONNECTED positions For the VCPW VSR the device is a drive screw and drive nut Although the device is mounted in the switchgear compartment a...

Page 16: ...IN SECTION 2 NOT FOLLOWING THE PROCEDURE MAY RESULT IN INCORRECT STARTER OPERATION LEADING TO DEATH BODILY INJURY AND PROPERTY DAMAGE When the starter is first commissioned into service and each time...

Page 17: ...tage for one minute Repeat for the remaining phases Successful withstand indicates satisfactory insulation strength of the primary circuit Open the starter Connect the high potential lead of the test...

Page 18: ...BE INSERTED INTO THE INTENDED STRUCTURE WARNING ARC FLASH INCIDENCES WITH MV SWITCHGEAR CAN OCCUR DURING THE PROCESS OF INSERTING AND REMOVING VSR UNITS IN SWITCHGEAR CUBICLES IT IS STRONGLY RECOMMEND...

Page 19: ...with the structure mounted racking shaft Figure 5 9 Turn the racking in crank in a clockwise direction and the VSR will move slowly toward the rear of the structure When the VSR reaches the CONNECTED...

Page 20: ...8 Install the bolt securing the vacuum interrupter to the upper terminal do not tighten 9 Install bolt and shunt supports securing lower terminal to housing Figure 6 6 When tightening insure laminated...

Page 21: ...pplied the contactor should close cleanly When power is removed the moving armature should securely contact the stop assembly 6 3 Control Board Check and Replacement To verify the output of the contro...

Page 22: ...he coil has the proper resistance connect an ohmmeter across the coil leads where they are connected to the bridge rectifier Refer to Table 6 1 for the correct impedance for the different voltage coil...

Page 23: ...LLATION 1 Remove the existing roller bracket from the contactor moving armature if one is attached 2 Secure the new roller bracket and bearing assembly with two 6mm x 25mm bolts with lock washers and...

Page 24: ...ER TO CONTACTOR COIL IF VOLTAGE IS BACK FED INTO A TRANSFORMER HIGH VOLTAGE WILL BE GENERATED ON THE TRANSFORMER PRIMARY HIGH VOLTAGE CAN CAUSE SERIOUS INJURY OR DEATH 6 Apply force to latch assembly...

Page 25: ...clear barrier in place and can be lifted straight up for access to the fuse hardware Figure 7 1 2 To remove the side phase barrier for access to the outer fuse lift the phase barrier straight up and...

Page 26: ...Part Number Description 2147A58G02 Vacuum Interrupter Assembly for SL 160 200 320 400 2147A58G03 Coil Control Board 2147A58G04 Auxiliary Contact Kit 2NO 2NC 2147A58G05 Auxiliary Contact Kit 3NO 3NC fo...

Page 27: ...27 Instruction Book IB02707112E August 2015 50 75VCPW VSR BreakerTo Vacuum Starter Replacement Unit EATON CORPORATION www eaton com...

Page 28: ...or Avenue Cleveland OH 44114 USA Eaton com 2014 Eaton Corporation All Rights Reserved Printed in USA Publication No IB02707112E August 2015 Eaton is a registered trademark of Eaton Corporation All tra...

Reviews: