Instruction Book 

IB02707112E

August 2015

50/75VCPW-VSR

Breaker To Vacuum Starter Replacement Unit

EATON CORPORATION www.eaton.com

4.3  SECONDARY DISCONNECTS

The VSR control circuit is connected to the switchgear control 

through a multi-contact block (See Section 3 for component 

location). The movable secondary control contacts mounted on the 

unit are self-aligning, line-contact, slip-type connectors. The multiple 

finger arrangement on the unit makes contact with a stationary 

mounted element. The contact surfaces on the stationary element 

are recessed to prevent accidental short-circuiting of the control 

circuits.
These secondary disconnects mate in both the operating and test 

positions. No special jumper is required.
Mechanical stops prevent over-travel and avoid damage to the 

disconnecting devices when the unit is racked into operating 

position.

 WARNING

INTERLOCKS ARE PROTECTIVE DEVICES FOR PERSONNEL AND 

EQUIPMENT. DO NOT BYPASS, MODIFY, OR MAKE INOPERATIVE ANY 

INTERLOCKS. DOING SO COULD CAUSE DEATH, SERIOUS PERSONNEL 

INJURY, AND/OR PROPERTY DAMAGE.

4.4  INTERLOCKS

There are several interlocks built into the VSR-Series vacuum 

starter replacements. Each of these interlocks, though different in 

form, duplicate or exceed in function that of the original breaker. 

These interlocks exist to safeguard personnel and equipment. The 

basic premise behind the interlocking arrangement on the vacuum 

replacement starter is that the starter must not be inserted into or 

remove from the live circuit while the main contacts are closed. 

Also considered in the interlocking is that the starter should pose no 

greater risk than necessary to the operator in or out of the cell. 

4.5  RACKING-IN INTERLOCK

The racking-in interlock is designed to prevent moving the starter 

into or out of the Connect position, if the starter contacts are closed. 

VCPW-VSR interlocks are completely compatible with the existing 

racking system located in the existing VCP-W assembly structure. 

VCPW-VSR starters utilize a interlock design that is very similar to 

the design used on VCP-W breakers. 

4.6  RACKING MECHANISM

The purpose of the racking device is to move the VSR between the 

TEST and CONNECTED positions. For the VCPW-VSR, the device 

is a drive screw and drive nut. Although the device is mounted 

in the switchgear compartment, a brief description here will help 

understand the operation. For additional information on the insertion 

and removal of a VSR from its compartment refer to the insertion 

and removal sections in this manual.
The racking device consists of a drive screw, a drive nut, two side 

rails and a sliding cage. In the TEST position, the nut is all the way 

to the front. As the VSR is pushed in, the racking latch snaps on the 

nut. Turning the crank clockwise while pushing forward advances the 

VSR toward the CONNECTED position. During this travel, the floor 

tripper TRIP roller is lifted up holding the VSR trip free. When the 

VSR reaches the CONNECTED position, the crank cannot be turned 

any further. A red flag indicates that the VCPW-VSR is fully engaged.
If the VSR is closed in the CONNECTED position, engagement of 

the slider will open the contactor and permit use of the racking 

crank. After tripping the VSR, the racking crank can be engaged and 

the VSR withdrawn to the TEST position by turning the racking crank 

counterclockwise. This position is indicated by no further motion of 

the crank.
The VCPW-VSR racking latch can be disengaged only when the VSR 

is in the TEST position by lifting the latch release. As the VSR is 

withdrawn, it comes out with the contacts open.

4.7  GROUND CONTACT

The ground contact is an assembly of spring loaded fingers for all 

VCPW-VSR Vacuum Motor Starter Replacement designs providing a 

disconnectable means for grounding the starter chassis, after it has 

been inserted into a switchgear cell (Figure 4.6). The ground contact 

is located on the underside of the chassis next to the secondary 

contact block. An extension of the switchgear ground bus is secured 

to the cell floor in such a position to engage the ground contact 

automatically, when the starter is pushed into the Test position. It 

remains engaged in all positions from Test to and including Connect.

4.8  OPERATIONS COUNTER

All VCPW-VSR Vacuum Motor Starter Replacement Units are 

equipped with a mechanical operations counter (Figures 3.3). As the 

starter opens, the counter advances the reading by one.

Figurt 4.6. GrNund CNnoaco

Summary of Contents for 75VCPW-VSR

Page 1: ...August 2015 Instruction Book IB02707112E 50 75VCPW VSR Breaker To Vacuum Starter Replacement Unit 50VCPW VSR 350 390A Shown Supersedes May 2014 Effective...

Page 2: ...WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF E...

Page 3: ...AFETY CODES SAFETY STANDARDS AND OR REGULATIONS AS THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED TO THESE VACUUM STARTER REPLACEMENT UNITS ARE DESIGNED TO BE INSTALLED PURSUAN...

Page 4: ...ed as Cutler Hammer and or Eaton WARNING SATISFACTORY PERFORMANCE OF THESE UNITS ARE CONTINGENT UPON PROPER APPLICATION CORRECT INSTALLATION AND ADEQUATE MAINTENANCE THIS INSTRUCTION BOOK MUST BE CARE...

Page 5: ...Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H I J K 50VCPW VSR 250 230A 390A 29 44 29 12 10 00 29 81 12 00 13 63 27 80 29 56 2 25 20 88 24 63 50VCPW VSR 350 230A 390A 31 44 2...

Page 6: ...any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a unit with the secondary test coupler engaged Failure to d...

Page 7: ...ntact Wear Gauge Optional item used to check contact wear Style 5259C11H01 See Section 5 Racking Handle The original VCP W racking handle is used to assist in moving the MV VSR into and out of the cel...

Page 8: ...falling objects excessive moisture etc must be provided Containers should be arranged to permit free circulation of air on all sides and temporary heaters should be used to minimize condensation Mois...

Page 9: ...ement Unit EATON CORPORATION www eaton com Figure 3 3 Front External View of 50VCPW VSR Front External View 1 Lifting Point 4 Push To Open Button 7 Lift Pull Handle 2 Extension Rail Interlock 5 Main C...

Page 10: ...75VCPW VSR BreakerTo Vacuum Starter Replacement Unit EATON CORPORATION www eaton com Figure 3 4 Rear External View of 50VCPW VSR Rear External View 1 Fuse 3 Phase Barrier 5 Primary Disconnects 2 Lifti...

Page 11: ...losing circuit which remains made while the contactor is being racked between the Test and Connected positions Consequently it prevents the starter from closing automatically even though the control s...

Page 12: ...iliary Contacts 12 Optional Auxiliary Contacts 6 Coil Control Board Terminal Block 13 Stop Assembly 7 Axial Magnetic Coil 3 SL400 Only 14 Base Plate SL Back View Major Components 1 Rear Mounting Holes...

Page 13: ...be wired in parallel with the a contacts on the Electro MOC The original b contacts must be wired in series with the b contacts on the Electro MOC It is suggested that polarized voltages should not b...

Page 14: ...arters are made of glass polyester They are all easily removed for access to the fuses Table 4 2 Electro MOC Contact Ratings Contact Circuit Volts Short Time Rating Amps Continuous Rating Amps Interru...

Page 15: ...the racking device is to move the VSR between the TEST and CONNECTED positions For the VCPW VSR the device is a drive screw and drive nut Although the device is mounted in the switchgear compartment a...

Page 16: ...IN SECTION 2 NOT FOLLOWING THE PROCEDURE MAY RESULT IN INCORRECT STARTER OPERATION LEADING TO DEATH BODILY INJURY AND PROPERTY DAMAGE When the starter is first commissioned into service and each time...

Page 17: ...tage for one minute Repeat for the remaining phases Successful withstand indicates satisfactory insulation strength of the primary circuit Open the starter Connect the high potential lead of the test...

Page 18: ...BE INSERTED INTO THE INTENDED STRUCTURE WARNING ARC FLASH INCIDENCES WITH MV SWITCHGEAR CAN OCCUR DURING THE PROCESS OF INSERTING AND REMOVING VSR UNITS IN SWITCHGEAR CUBICLES IT IS STRONGLY RECOMMEND...

Page 19: ...with the structure mounted racking shaft Figure 5 9 Turn the racking in crank in a clockwise direction and the VSR will move slowly toward the rear of the structure When the VSR reaches the CONNECTED...

Page 20: ...8 Install the bolt securing the vacuum interrupter to the upper terminal do not tighten 9 Install bolt and shunt supports securing lower terminal to housing Figure 6 6 When tightening insure laminated...

Page 21: ...pplied the contactor should close cleanly When power is removed the moving armature should securely contact the stop assembly 6 3 Control Board Check and Replacement To verify the output of the contro...

Page 22: ...he coil has the proper resistance connect an ohmmeter across the coil leads where they are connected to the bridge rectifier Refer to Table 6 1 for the correct impedance for the different voltage coil...

Page 23: ...LLATION 1 Remove the existing roller bracket from the contactor moving armature if one is attached 2 Secure the new roller bracket and bearing assembly with two 6mm x 25mm bolts with lock washers and...

Page 24: ...ER TO CONTACTOR COIL IF VOLTAGE IS BACK FED INTO A TRANSFORMER HIGH VOLTAGE WILL BE GENERATED ON THE TRANSFORMER PRIMARY HIGH VOLTAGE CAN CAUSE SERIOUS INJURY OR DEATH 6 Apply force to latch assembly...

Page 25: ...clear barrier in place and can be lifted straight up for access to the fuse hardware Figure 7 1 2 To remove the side phase barrier for access to the outer fuse lift the phase barrier straight up and...

Page 26: ...Part Number Description 2147A58G02 Vacuum Interrupter Assembly for SL 160 200 320 400 2147A58G03 Coil Control Board 2147A58G04 Auxiliary Contact Kit 2NO 2NC 2147A58G05 Auxiliary Contact Kit 3NO 3NC fo...

Page 27: ...27 Instruction Book IB02707112E August 2015 50 75VCPW VSR BreakerTo Vacuum Starter Replacement Unit EATON CORPORATION www eaton com...

Page 28: ...or Avenue Cleveland OH 44114 USA Eaton com 2014 Eaton Corporation All Rights Reserved Printed in USA Publication No IB02707112E August 2015 Eaton is a registered trademark of Eaton Corporation All tra...

Reviews: