Step 7
Install LRTP into T-Body
•
Clean and then lubricate the mating 600 A interface of
the LRTP and T-body with the lubricant supplied.
•
Remove and recycle the shipping cap from the 200 A
LRTP interface and the thread protector from the
alignment segment.
•
Insert T-Wrench into throat of LRTP and thru rotating nut
and engage alignment segment. (T-Wrench should not
rotate without entire LRTP rotating.)
•
Insert the 600 A alignment segment end of the LRTP into
the side of T-body opposite the apparatus bushing. (Refer
to Figure 8.)
•
Carefully thread the alignment segment into the threads
of compression connector by turning the T-Wrench
clockwise until a positive stop is felt.
•
Continue applying clockwise force to the T-Wrench until
the pin connecting the alignment segment to the LRTP
shears allowing the T-Wrench and alignment segment to
rotate freely.
•
Remove alignment segment by applying pressure to the
T-Wrench to separate the alignment segment from the
LRTP. Recycle the align ment segment.
•
See Figure 9 for illustration of completed LRTP
installation.
Step 8
Install probe
•
Place tin plated copper PUSH-OP probe with stud on
5/16" hex T-Wrench.
•
Insert 5/16" hex T-Wrench into end of the probe and align
with the exposed extended length threads of the stud-T
with the internal floating nut of the LRTP.
ote:
N
Do not cross thread probe on floating nut.
•
Insert torque wrench into the throat of the LRTP to
engage the floating nut.
•
Holding probe in place with 5/16" hex T-Wrench, tighten
probe until torque tool begins to ratchet (20 to 25 ft. lbs.).
(Refer to Figure 10.)
•
Remove Tools
Figure 10. Line illustration of probe installation.
TORQUE TOOL
PROBE
T-WRENCH
Align with internal
floating nut of
LRTP
Figure 8. LRTP installation into T-body.
T-WRENCH
LRTP
CLEAN AND
LUBRICATE
ALIGNMENT
SEGMENT
PUSH-OP T-BODY
Figure 9. LRTP permanently installed into T-body forming
the PUSH-OP assembly.
LRTP
T-BODY
EXTENDED
STUD
T-WRENCH
SEPARATED
ALIGNMENT
SEGMENT
PUSH-OP ASSEMBLY
LRTP
4
600 A 15/25 KV CLASS PUSH-OP DEADBREAK CONNECTOR INSTALLATION INSTRUCTIONS
MN650057EN May 2017