Installation instructions
Equipment required
•
PUSH-OP Deadbreak Connector Assembly Kit including:
•
PUSH-OP Body
•
Cable Adapter
•
Coppertop Compression Connector
•
Loadbreak Reducing Tap Plug (LRTP)
•
Protective Cap (when furnished)
•
Silicone Lubricant
•
Tin Plated Copper Contact Probe
•
Instruction Sheets
•
Tools
•
5/16" Torque Tool (Catalog Number TQHD625)
•
5/16" T-Wrench (Catalog Number TWRENCH)
Cable preparation
ote:
N
If a non-Eaton 600 A T-body is being used, use the
stripback lengths given in the T-body kit, then proceed
to Step 7 of these instructions.
Step 1
Train cable
•
Position cable so that it is centered between apparatus
bushing and parking pocket, parallel to apparatus
frontplate.
•
Provide adequate cable slack for cable movement
between standoff bushing and apparatus bushing.
•
Support cable as needed to maintain position.
•
Cut cable 1-3/4 inches (45 mm) from centerline of
bushing. (Refer to Figure 2.)
Step 2
Cutbacks for concentric neutral cable
•
If cable is not concentric neutral (metallic tape shielded,
longitudinally corrugated, wire shielded, or UniShield™)
use Eaton's SA series adapter kit with the same cutback
dimensions as concentric neutral below. If another
manufacturer’s metallic shield adapter is used, follow the
cutback instructions in the shield adapter kit.
•
Take care not to cut into the cable insulation.
Step 3
Install CA625 cable adapter
•
Cut a 45° chamfer into the end of the cable insulation.
•
Clean the cable insulation wiping towards the semi-con
insulation shield.
•
Apply a thin coating of the supplied lubricant to the cable
insulation and to the cable entrance of the cable adapter.
•
Slide cable adapter onto the cable until the black portion
of the adapter touches the vinyl tape marker.
Figure 2. Line illustration for cable training.
EXISTING
BUSHING
CABLE
1
3
/
4
"
(45 mm)
Figure 4. Install the cable adapter.
CABLE INSULATION
CLEAN AND LUBRICATE
TAPE MARKER
CHAMFER
CA625
{
Figure 3. Cutback dimensions for concentric neutral
cable.
CONCENTRIC
NEUTRAL WIRES
CABLE
JACKET
VINYL TAPE
MARKER
EXTRUDED SEMI-CON
INSULATION SHIELD
CABLE INSULATION
9
3
/
4
" (248 mm)
10
3
/
4
" (273 mm)
12
3
/
4
" (324 mm)
2
600 A 15/25 KV CLASS PUSH-OP DEADBREAK CONNECTOR INSTALLATION INSTRUCTIONS
MN650057EN May 2017