background image

22

Instruction Book    

IB182017EN   February 2017   www.eaton.com

5kV, 7.5kV, & 15kV DHP-VR

Replacement Circuit Breaker

a. Breaker open, closing springs discharged.
b. Breaker open, closing springs charged.
c. Breaker closed, closing springs discharged.
d. Breaker closed, closing springs charged.

The mechanism is a mechanically “trip-free” design. Trip-free is 

defined later in this section.
In normal operation the closing spring is charged by the spring 

charging motor, and the breaker is closed electrically by the 

switchgear control circuit signal to energize the spring release coil. 

Tripping is caused by energizing the trip coil through the control 

circuit.
For maintenance inspection purposes the closing springs can be 

charged manually by using the maintenance tool and the breaker can 

be closed and tripped by pushing the “Push to Close” and “Push to 

Open” buttons on the front panel.

 WARNING

KEEP HANDS AND FINGERS AWAY FROM BREAKER’S INTERNAL PARTS 

WHILE THE BREAKER CONTACTS ARE CLOSED OR THE CLOSING SPRINGS 

ARE CHARGED. THE BREAKER CONTACTS MAY OPEN OR THE CLOSING 

SPRINGS DISCHARGE CAUSING CRUSHING INJURY. DISCHARGE 

THE SPRINGS AND OPEN THE BREAKER BEFORE PERFORMING ANY 

MAINTENANCE, INSPECTION OR REPAIR ON THE BREAKER.

THE DESIGN OF THIS CIRCUIT BREAKER ALLOWS MECHANICAL CLOSING 

AND TRIPPING OF THE BREAKER WHILE IT IS IN THE “CONNECT” 

POSITION. HOWEVER, THE BREAKER SHOULD BE CLOSED MECHANICALLY 

ONLY IF THERE IS POSITIVE VERIFICATION THAT LOAD SIDE CONDITIONS 

PERMIT. IT IS RECOMMENDED THAT CLOSING THE BREAKER IN THE 

“CONNECT” POSITION ALWAYS BE DONE WITH THE CUBICLE DOOR 

CLOSED. FAILURE TO FOLLOW THESE DIRECTIONS MAY CAUSE DEATH, 

PERSONAL INJURY, OR PROPERTY DAMAGE.

ELECTRICAL TRIPPING CAN BE VERIFIED WHEN THE BREAKER IS IN THE 

“DISCONNECT / TEST” POSITION.

4.4.1   CLOSING SPRING CHARGING

Figure 4.15 shows schematic section views of the spring charging 

parts of the stored energy mechanism.
The major component of the mechanism is a cam shaft assembly 

which consists of a shaft to which are attached two closing spring 

cranks (one on each end), the closing cam, drive plate, and a free-

wheeling ratchet wheel.
The ratchet wheel (6) is actuated by an oscillating ratchet lever 

(12) and drive pawl (10) driven by the motor eccentric cam. As the 

ratchet wheel rotates, it pushes the drive plates which in turn rotate 

the closing spring cranks and the closing cam on the cam shaft. 

The motor will continue to run until the limit switch “LS” contact 

disconnects the motor.
The closing spring cranks have spring ends connected to them, 

which are in turn coupled to the closing springs. As the cranks 

rotate, the closing springs get charged.
The closing springs are completely charged, when the spring cranks 

go over dead center and the closing stop roller (9) comes against the 

spring release latch (1). The closing springs are now held in the fully 

charged position.
The closing springs may also be charged manually as follows: Insert 

the end of the maintenance tool into the manual charge socket 

opening and charge the closing springs by moving the handle up 

and down the full range of motion. When charging is complete the 

ratchet will no longer advance and the spring charged / discharged 

indicator displays “charged”. (Figure Set 3.3). Any further motion of 

the maintenance tool will not result into advance of charging.

4.4.2   CLOSING OPERATION

Figure 4.16 shows the positions of the closing cam and tripping 

linkage for four different operational states. In Figure 4.16.a the 

breaker is open and the closing springs are discharged. In this state, 

the trip latch is disengaged from the trip “D” shaft (unlatched). After 

the closing springs become charged, the trip latch snaps into the 

fully reset or latched position (Figure 4.16.b)
When the spring release clapper (Figure 4.15, Item 13) moves into 

the face of the spring release coil (electrically or manually), the upper 

portion of the clapper pushes the spring release latch (1) upward. 

When the spring release latch moves, the cam shaft assembly is 

free to rotate. The force of the closing cam (Figure 4.16.b, Item 5), 

moving the main link (2), rotating the pole shaft (4) (which charges 

the opening spring). This moves the three operating rods (3), closes 

the main contacts and charges the contact loading springs (not 

shown). The operational state immediately after the main contacts 

close but before the spring charging motor recharges the closing 

springs is illustrated in Figure 4.16.c. Interference of the trip “D” 

shaft with the trip latch prevents the linkage from collapsing, and 

holds the breaker closed.
Figure 4.16.d shows the breaker in the closed state after the closing 

springs have been recharged. The recharging of the spring rotates 

the closing cam one half turn. In this position the main link roller 

rides on the cylindrical portion of the cam, and the main link does 

not move out of position.

4.4.3   TRIPPING OPERATION

When the trip bar “D” shaft (Figure 4.16.b, Item 9) is turned by 

movement of the shunt trip clapper (11), the trip latch will slip past 

the straight cut portion of the trip bar shaft and will allow the banana 

link and main link roller to rise. The energy of the opening spring and 

contact loading springs is released to open the main contacts. The 

mechanism is in the state illustrated (Figure 4.16.b) after the breaker 

is tripped open.

4.4.4   TRIP-FREE OPERATION

When the manual trip button is held depressed, any attempt to close 

the breaker results in the closing springs discharging without any 

movement of the pole shaft or vacuum interrupter stem.

4.5   CONTROL SCHEMES

There are two basic control schemes for each series of Type VCP-WR 

breakers, one for DC control and one for AC control voltages (Figure 

4.5). Specific wiring schematics and diagrams are included with each 

breaker.
There may be different control voltages or more than one tripping 

element, but the principal mode of operation is as follows:
As soon as the control power is applied, the spring charging motor 

automatically starts charging the closing spring. When the springs 

are charged, the motor cut off LS1/bb switch turns the motor off. The 

breaker may be closed by making the control switch close (CS/C) 

contact. Automatically upon closing of the breaker, the motor starts 

charging the closing springs. The breaker may be tripped any time by 

making the control switch (CS/T) contacts.
Note the position switch (PS1) contact in the spring release circuit 

in the scheme. This contact remains made while the breaker is 

being racked between the TEST and CONNECTED positions for 

appropriately retrofitted breakers. Consequently, it prevents the 

breaker from closing automatically, even though the control close 

contact may have been made while the breaker is racked to the 

CONNECTED position.
When the CS/C contact is made, the  SR  closes the breaker. If 

the  CS/C contact is maintained after the breaker closes, the Y relay 

is picked up. The  Y/a contact seals in Y until CS/C is opened. The  

Y/b  contact opens the SR circuit, so that even though the breaker 

would subsequently open, it could not be reclosed before CS/C was 

released and remade. This is the anti-pump function.

Summary of Contents for 50DHP-VR

Page 1: ...February 2017 Instruction Book IB182017EN 5kV 7 5kV 15kV DHP VR Replacement Circuit Breaker Supersedes I B 6513C80G Effective 5kV DHP VR 1200A Shown...

Page 2: ...to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of particular equipment contact an Eaton representati...

Page 3: ...RLOCK 25 4 7 3 ANTI CLOSE INTERLOCK 25 4 7 4 FLOOR TRIPPING AND CLOSING SPRING RELEASE INTERLOCKS 25 4 7 5 RAIL LATCH 25 4 8 MISCELLANEOUS ITEMS 25 4 8 1 GROUNDING CONTACT 25 4 8 2 MOC AND TOC OPERATI...

Page 4: ...s VIBE is a digital supplemental booklet featuring user interactive content and informative videos intended to assist with the maintenance of the VR Series circuit breaker The VIBE document is availab...

Page 5: ...78 132 4 16 350 1200 2000 3000 50DHP350 1 19 19 60 41 49 78 132 75DHP VR 7 2 500 1200 2000 3000 75DHP500 1 25 36 95 33 41 66 111 75DVP VR 7 2 500 1200 2000 75DVP500 1 25 36 95 33 41 66 111 150DHP VR...

Page 6: ...kV DHP VR Replacement Circuit Breaker Table 2 DHP VR 5kV 250 MVA Rating Dimensions Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H I 50DHP VR 250 250U 1200 2000 48...

Page 7: ...15kV DHP VR Replacement Circuit Breaker Table 3 DHP VR 5kV 350 MVA Rating Dimensions Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H I 50DHP VR 350 1200 2000 57 1...

Page 8: ...V 7 5kV 15kV DHP VR Replacement Circuit Breaker Table 4 DHP VR 5kV 350 MVA Rating Dimensions Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H 50DHP VR 350 3000 61 1...

Page 9: ...Amps A B C D E F G 75DHP VR 500 1200 2000 3000 60 75 31 25 10 00 34 81 10 00 19 75 20 69 150DHP VR 500 1200 2000 3000 60 75 31 25 10 00 34 81 10 00 19 75 20 69 150DHP VR 750 1200 2000 3000 60 75 31 2...

Page 10: ...V 15kV DHP VR Replacement Circuit Breaker Table 6 DHP VR 15kV Ratng Dimensions Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F 150DHP VR 50G 1200 2000 3000 73 72 31 00...

Page 11: ...njury and or property damage Do not work on a breaker with the secondary test coupler engaged Failure to disconnect the test coupler could result in an electrical shock leading to death personnel inju...

Page 12: ...ch moves the circuit breaker into and out of the cell The original OEM racking handle will interface with the VR Series replacement breaker racking mechanism and is therefore not provided as part of t...

Page 13: ...this initial check leave the closing springs discharged and breaker contacts open Outdoor storage is NOT recommended If unavoidable the outdoor location must be well drained and a temporary shelter fr...

Page 14: ...VR 250 1200A Shown Front External View 1 Pull Push Handle 6 Code Plate 11 Push To Open Button 2 Operations Counter 7 Secondary Contact Operating Rod 12 Racking Operating Shaft 3 Breaker Contact Statu...

Page 15: ...ing Outer Phase Barrier Removed For Demonstration Purposes Rear External View 1 Lifting Point 5 Phase Barrier 9 Racking Nut Housing 2 Vacuum Interrupter 6 V flex Current Connectors 10 Secondary Discon...

Page 16: ...DHP VR 500 2000A Shown Front External View 1 Pull Push Handle 5 Code Plate 9 Spring Charged Discharged Indicator 2 Operations Counter 6 Secondary Engaging Handle 10 Racking Operating Shaft 3 Breaker C...

Page 17: ...igure 3 3 d Rear External View of 7 5 and 15kV DHP VR 150DHP VR 500 2000A Shown Rear External View 1 Lifting Point 4 Guide Channel 7 Snubber Bolt 2 Racking Nut Housing 5 Phase Barrier 8 Secondary Disc...

Page 18: ...VR 50G Front External View 1 Operations Counter 5 Secondary Engaging Handle 9 Spring Charged Discharged Indicator 2 Breaker Contact Status Indicator 6 Removable Faceplate 10 Racking Operating Shaft 3...

Page 19: ...rcuit Breaker Figure 3 3 f Rear External View of 15kV DHP VR 50G Rear External View 1 Lifting Point 4 Phase Barrier 7 Racking Nut Housing 2 MOC Switch Operating Mechanism 5 Primary Disconnect Contact...

Page 20: ...g a restrike across the gap of the open contacts 4 1 1 THE INTERRUPTER ASSEMBLY Each interrupter is assembled at the factory as a unit to assure correct dimensional relationships between working compo...

Page 21: ...ADJUSTMENTS OF CONTACT WIPE AND STROKE ALL SUCH ADJUSTMENTS ARE FACTORY SET AND SHOULD NOT BE ATTEMPTED IN THE FIELD 4 2 PHASE BARRIERS Phase barriers are sheets of insulation located between the inte...

Page 22: ...In Figure 4 16 a the breaker is open and the closing springs are discharged In this state the trip latch is disengaged from the trip D shaft unlatched After the closing springs become charged the tri...

Page 23: ...pt between Test and Connect positions OPERATION C and NO C and NC C and NO C and NO C and NC C and NO Brown Switch Black Switch Black Switch Brown Switch SWITCH TERMINAL LS1 bb LS2 aa LS2 bb LC PS1 PS...

Page 24: ...in conjunction with regular maintenance periods to assist in tracking the general health of the breaker Typical ranges as observed using nominal control voltages are listed in Table 4 Table 4 Time Pe...

Page 25: ...When the breaker is closed the interlock component moves away from the spring release clapper so that it cannot lift the spring release latch 9 4 7 4 FLOOR TRIPPING AND CLOSING SPRING RELEASE INTERLOC...

Page 26: ...ing by one 4 8 4 RACKING DEVICE The purpose of the racking device is to move the breaker between the Test and Connected positions On the 7 5 or 15kV DHP VR the racking mechanism is located in the mech...

Page 27: ...Element Front Faceplate Removed 20WR Vacuum Element 1 LH Closing Spring 5 Closing Cam 9 Reset Opening Spring 2 Motor Cutoff Switch 6 Spring Release Assembly 10 Manual Charge Socket 3 Latch Check Swit...

Page 28: ...Element Front Faceplate Removed 29WR Vacuum Element 1 LH Closing Spring 5 Closing Cam 9 Reset Opening Spring 2 Motor Cutoff Switch 6 Spring Release Assembly 10 Manual Charge Socket 3 Latch Check Swit...

Page 29: ...atch 6 Ratchet Wheel 11 Anti Close Interlock 2 Pole Shaft 7 Spring Crank 12 Motor Ratchet Lever 3 Closing Spring Fixed End 8 Cam Shaft 13 Spring Release Close Clapper 4 Closing Spring 9 Spring Release...

Page 30: ...c Breaker Closed and Closing Spring Not Charged 4 16 b Breaker Open and Closing Spring Charged 4 16 d Breaker Closed and Closing Spring Charged Figure 4 16 Charging Schematic Charging Schematic 1 Main...

Page 31: ...tment is checked and compatible if the breaker is moved to a different housing of the same rating The breaker has been factory adjusted to operate one mechanism operated cell MOC switch in the cell Th...

Page 32: ...REPLACEMENT DHP VR CIRCUIT BREAKER FAILURE TO COMPLETE THESE STEPS COULD RESULT IN EQUIPMENT DAMAGE AND OR IMPROPER OPERATION Inspect the MOC pantograph in keeping with the following steps and refer...

Page 33: ...nubber bolts on each side of the breaker Figure 5 8 Step 2 Adjust the height of the top of the snubber bolt to be between 0 0 and 0 031 0 0 and 1 32 inches below the measured height of the current tra...

Page 34: ...PPROPRIATE BEFORE PROCEEDING Press down on the rail latch on the front right side of the breaker with your foot and push the breaker toward the rear of the cell as far as it will go Be sure the breake...

Page 35: ...connected Withstand 1125V 60Hz For 1 Minute Hipot Tester Clean And Retest Or Replace 2 Power Element Vacuum Interrupters Contact Erosion Visibility Of Mark Visual Close The Breaker And Look For Green...

Page 36: ...electrical charge that may be retained particularly from the center shield of vacuum interrupters To avoid any ambiguity in the AC high potential test due to leakage or displacement capacitive current...

Page 37: ...ngth of the primary circuit Open the breaker Connect the high potential lead of the test machine to one of the poles of the breaker Connect the remaining poles and breaker frame to ground Start the ma...

Page 38: ...sure of the extra energy available in terms of over travel in inches to close the breaker contacts to their full extent It may be used periodically to monitor the health of the mechanism General Infor...

Page 39: ...ify that the mark made in Step 7 is aligned with the pen opening If it is not aligned this indicates a problem with the circuit breaker stop the test and consult the factory Step 12 Inspect the circui...

Page 40: ...ove the Sharpie 15o Left and Right Figure 6 13 Top view of Cam and Marker Interface Cam Marker CloSure Tool TM 15O 15O Figure 6 10 With Marker in Hole C While Closing Breaker Figure 6 8 Manually Charg...

Page 41: ...ft the cam shaft the main link and the motor eccentric These bearings are packed at the factory with a top grade slow oxidizing grease which normally should be effective for many years They should not...

Page 42: ...d Motor Cut Off Contacts Open Or Burned Trip Coil Assembly Clapper Fails To Reset Closing Sound But No Close Pole Shaft Not Open Fully Trip Latch Reset Spring Damaged Or Missing Trip Bar D Shaft Fail...

Page 43: ...SWITCH Breaker Auxiliary Switch 94C9525G13 5 BREAKER POSITION SWITCH Breaker Position Switch PS1 94C9525H06 6 BREAKER POSITION SWITCH Breaker Position Switch PS2 94C9525H07 7 LATCH CHECK SWITCH Latch...

Page 44: ...evard Cleveland OH 44122 United States Eaton com 2017 Eaton All Rights Reserved Printed in USA Publication No IB182017EN February 2017 Eaton is a registered trademark All trademarks are property of th...

Reviews: