Figure 38.
Wiring diagram of the 120 and 160 kVA Tie cabinet
Please refer to main User’s and Installation Guide (1022403) for sizing cables
Wiring procedure:
1.
If not already open, unfasten front door latch and swing door open.
2.
Remove the door by opening a screw from the bottom hinge.
3.
Place the door to its correct position.
4.
Remove the switches S11, S21, S31 and the screws from the plate.
5.
Remove cabinet top or bottom wire entry landing plate to drill or punch wire ways.
Cartridge fuse list (S11, S21, S31)
UPS size
Type
Rating
Size (IEC269)
P/N
120 kVA
gL/gG
200 A 690 VAC
2NH
8052350
160 kVA
gL/gG
250 A 690 VAC
2NH