UPS 40 – 160 kVA, 400V 50/60 Hz output
User’s and Installation Guide
1023294
Revision C
69
12.5 System DC circuit
UPS
40 kVA
60,80 kVA
100, 120 kVA
160 kVA
Battery monitoring
Advanced Battery Management (ABM™)
Battery type
VRLA 12 Volts
Battery qty
40 pcs.
Nominal voltage
480 Volts (240 cells)
Float voltage
2.30 VPC
Cut off voltage
1.70 VPC with 2 min countdown timer; 1.56 VPC absolute value
Battery charging
10 A
20 A
30 A
40 A
12.6 System output
UPS
40 kVA
60,80 kVA
100, 120 kVA
160 kVA
Active power
36 kW
54, 72 kW
90, 108 kW
144 kW
Voltage
220/380V, 230/400V, 240/415V, user selectable
Frequency
50 or 60 Hz, user selectable
Voltage regulation
± 1% (10% to 100% load)
Harmonics
3% VHD at nominal linear load condition
Nominal current
57 A
93 A, 115 A
145 A, 173 A
232 A
Short-circuit current
120 A, 300 ms
240 A 300 ms
360 A, 300 ms
480 A, 300 ms
Overload
110% for 10 min (with no bypass available)
125% for 30 sec. (with no bypass available)
150% for 10 sec. (with no bypass available)
1000% for 20 msec. (with integral static bypass)
110% for 60 min (mains available)
125% for 10 min (mains available)
150% for 1 min (mains available)