UPS 40 – 160 kVA, 400V 50/60 Hz output
User’s and Installation Guide
1023294
Revision C
21
4.3.1 Integral battery cabinet installation procedure
This procedure assumes the battery cabinet is located to the left of the UPS cabinet.
Warning!
The battery cabinet contains lethal voltages. Qualified service personnel should perform
installation and service only.
1.
Make sure that the UPS is properly installed and secured with its levelling feet.
2.
Roll the battery cabinet to an area near the left-hand side of the UPS.
3.
Remove the field kit. The field kit is attached with cable ties to the frame inside the door.
Retain the field kit for later use.
4.
If necessary, remove the cosmetic cover and hanger brackets from the left-hand side of the
UPS. Save cover, screws, and brackets for later reuse.
5.
If necessary, remove the cosmetic cover and hanger brackets from the right-hand side of
the battery cabinet. Save cover, screws, and brackets for later reuse.
6.
Remove the knockout plug on the bottom left side of the UPS cabinet inside panel.
Figure 12.
Location of the knockout plugs in the UPS unit.
7.
Install nylon grommet from field kit around hole left after removal of knockout plug.
8.
Push the battery cabinet toward the UPS cabinet until the doors are flush with each other.
Level the cabinets with the levelling screws.
9.
Two cabinet attachment brackets are provided for securing each cabinet at the top and
bottom. A flat bracket joins the top of the cabinets and a larger flat bracket joins the
cabinets at the bottom. Attach the flat bracket to the cabinet tops first.
10. Remove the left-hand screw from the top door hinge of the UPS cabinet and the right-
hand screw from the top right door hinge of the battery cabinet. Align the holes in the
small flat bracket from the field kit over these screw holes. Replace the screws in the
hinges, securing the bracket to the cabinets.