3. Installation
3.6 Preparing the device for operation
Grounding option
If required due to the installation environment, this Connection lug 4.8 x 0.8 mmcan be used as a protective
earth connection.
One compatible cable lug option would be the Phoenix Contact C-SCFFI 1.5/4.8X0.8 slip-on sleeve with part
No. 3240537 (not included).
Specifications for connection to 24 VDC power supply (-20%/+25%):
Tightening tor-
que
0.22 ... 0.25 Nm
for the screws on the MC 1.5/ 2-ST-3.5 BK
Strip length
7 mm (0.28“)
Connect the individual conductors.
Solid
0.14 to 1.5 mm²
Flexible
0.14 to 1.5 mm²
Insulated ferrule
0.25 to 0.5 mm²
Non-insulated ferrule
0.25 to 1.5 mm²
Conductor cross section AWG
min 28 - max 16
Tab. 4: Terminal capacities
Power Supply
+24 V DC
0 V
U
e
= 24 V DC
(19.2 - 30 V DC)
I
e
≦ 0.3 A
0 V
+24 V
DC
0.22 - 0.25 Nm
(1.94 - 2.21 lb-in)
2.5 mm
Fig. 9: Connecting the screw terminals on the plug connector
easy Remote Touch display
06/21 MN048027EN Eaton.com
43