10 Wiring
14
ESR5-NV3-300
12/19 MN049006EN
www.eaton.com
10 Wiring
▶
Connect the cables to the connection terminal blocks using a
screwdriver.
Figure 9:
Connecting the cables
10.1 Signal generator connection versions
▶
Connect suitable signal generators to S10/S11/S12 and S21/S22.
Figure 10:Signal generator connection versions
a
Two-channel connection with cross-circuit monitoring
b
Two-channel connection without cross-circuit monitoring
c
Single-channel connection
→
It is recommended that ferrules are used to connect stranded
cables.
→
For compliance with UL approval, use copper wire that is
approved
up
to 60 °C/75 °C.
A
B
AWG 24-12
0.2 - 2.5 mm
2
7 mm
(0.28“)
0.5 - 0.6 Nm
(5 - 7 lb-in)
S11
S10
S22
S21
S12
24 V DC
24 V DC
①
②
③
24 V DC
0 V
0 V
0 V
S11
S10
S22
S21
S12
S11
S10
S22
S21
S12