17 Technical data
ESR5-NV3-300
12/19 MN049006EN
www.eaton.com
23
17 Technical data
Input data
Nominal input voltage U
N
24 V DC -15 % / +10 %
Typical input current
155 mA
Typical inrush current
200 mA (at U
N
)
< 40 mA (with U
N
/I
x
to S10)
< 150 mA (with U
N
/I
x
to S12)
> -60 mA (with U
N
/I
x
to S22)
< 40 mA (with U
N
/I
x
to S34)
< 40 mA (with U
N
/I
x
to S35)
Current consumption
< 40 mA (with U
N
/I
x
to S10)
< 50 mA (with U
N
/I
x
to S12)
> -40 mA (with U
N
/I
x
to S22)
0 mA (with U
N
/I
x
to S34)
< 5 mA (with U
N
/I
x
to S35)
Power consumption at U
N
, typical
3.72 W
Voltage at input/start and feedback circuit
24 V DC -15 % / +10 %
Max. permissible overall conductor resistance
∼
22
Ω
(Input and reset circuit at U
N
)
Typical response time
< 600 ms (automatic start)
< 70 ms (manual start)
Typical starting time with U
N
600 ms (when controlled via A1)
Typical release time with U
N
< 20 ms (when controlled via S11/S12 and S21/S22)
< 20 ms (when controlled via A1)
Delay time range
0.2 s - 300 s ±20 % (K3(t), K4(t) can be parameterized)
Recovery time
< 1 s
Maximum switching frequency
0.5 Hz
Concurrence input 1/2
∞
Operating voltage display
1 x LED, green
Status display
4 x LEDs, green
Protective circuit
Surge protection Suppressor diode
Output data
Contact type
3 enabling current paths undelayed
2 enabling current paths delayed
1 signaling current path undelayed
Contact material
AgSnO
2
Minimum switching voltage
5 V AC/DC
Maximum switching voltage
250 V AC/DC (observe the load curve)
Limiting continuous current
6 A (N/O contact, pay attention to the derating)
6 A (N/C contact)
Maximum inrush current
20 A (
Δ
t
≦
100
ms, undelayed contacts)
8 A (delayed contacts)
Inrush current, minimum
10 mA
Sq. Total current
(I
TH
)
2
=
(I
1
)
2
+ (I
2
)
2
+ … + (I
n
)
2
55 A
2