Page viii
IB131021EN
Effective Mar 2018
Spin-Free Levering-In Crank:
Used to crank breaker
between TEST and CONNECTED positions (Style
701B601G11).
Extension Rails:
Permits breaker to be withdrawn from its
compartment (Style 7813C41G03 for VCP-WL).
Rail Clamps:
Used to secure breaker to extension rails
(Style 6511C83G11 for VCP-WL).
Lifting Yoke:
Used to lift breaker (Style 691C607G11 for
VCP-WL).
Drawout Ramp:
Used to insert or withdraw breaker from
lower
compartment
without
portable
lifter
(Style
1C14163G02 for VCP-WL).
Portable Lifter:
Used to lift breaker to or from extended
rails (Style 1C14504H01).
Docking Transport Dolly:
Used to insert or withdraw
breaker from lower compartment without portable lifter or
move breaker from one location to another (Style
6510C71G11 for VCP-WL).
Electrical Levering-In Device:
Used to electrically move
breaker between TEST and CONNECTED positions (Style
1A30257G01).
Test Jumper:
Used to operate breaker electrically while
breaker is on extension rails or transport dolly (Style
6526C23G11 for VCP-WL).
Test Cabinet:
Used to provide power to operate breaker
outside its compartment (Styles 8346A28G21 – G23 for
VCP-WL depending on voltage requirements).
3-6
TYPE VCP-WL VACUUM CIRCUIT BREAKER
ELEMENT WEIGHTS (TABLE 3.1)
Table 3-1 VCP-WL ANSI Rated Breaker Weights
①
Rating
Amperes
Lbs. (kg)
50VCP-WL25
1200
350
75VCP-WL25
1200
350
150VCP-WL25
1200
350
Does not include shipping carton