CV3100 series and MINI series high performance general purpose inverter instruction manual
5-16
Senior Function
Function
Code
Name &
Definition
Set Range
Minimun
Unit
Factory
Default
Communi
cation
Address
Modify
PA.00
Zero
frequency
running
threshold
0.00
~
50.00Hz
0.01Hz
0.00Hz
0A00H
○
PA.01
Zero
frequency
hysteresis
0.00
~
50.00Hz
0.01Hz
0.00Hz
0A01H
○
PA.02
Energy
consuming
brakinginiti
al voltage
600
~
750V
1V
700V
0A02H
○
PA.03
Energy
consuming
braking
action
percentage
10
~
100
%
1%
50
%
0A03H
○
PA.04
Input
phase-failur
e protection
& Cooling
fan control
0
:
Enable & Fan automatic control
1
:
Enable & Fan working during
power on
2
:
Disable & Fan automatic control
3
:
Disable & Fan working during
power on
1
0
0A04H
○
PA.05
UP/DOWN
terminal
modifying
speed
0.01Hz
~
100.0Hz/S
0.01Hz/S
1.00Hz/
S
0A05H
○
PA.06
Over
modulation
enabling
0
:
Forbidden
1
:
Allowable
1
0
0A06H
×
PA.07
Timer
value seting
0
~
65536S
1S
0
0A07H
×
PA.08
The Rang
of AO1
output
0
:
0
~
10V/0
~
20mA
1
:
2
~
10V/4
~
20mA
1
0
0A08H
×
PA.09
Reserved
PA.10
Reserved
PA.11
Reserved
PA.12
Reserved