CV3100 series and MINI series high performance general purpose inverter instruction manual
3-13
Type
Terminal
no.
Name
Terminal function
Spec.
Analog input
AI1
Analog input AI1
Accept the input of analog
voltage( Reference
ground: GND)
Input voltage range:
0~10V (input
impendence: 94KΩ)
Resolution
:
1/1000
AI2
Analog input AI2
Accept input of analog
current and voltage
(Reference ground:
GND), diagram 3-9 is
referred, select by dip
switch on the left side of
control terminal.
Input current range:
0~20mA (input
impendence: 500Ω)
Resolution
:
1/1000
Analog output
AO1
Analog output
AO1
Provide analog voltage
output, can express 8
analog quantity, output
frequency as factory
default (Reference
ground: GND)
Voltage output range
:
0~10V/0-20mA;
2~10V/4-20mA
Running
control
terminal
FWD
Forward running
order
Forward/reverse digital
command, is referred to
introduction of function
parameter two-wire and
three-wire control
function
Optic-coupling isolation
input
Input impendence:
R=2KΩ
Max input
frequency:200Hz
Input voltage: 9
~
30V
Closing available
REV
Reverse running
order
Multi-function
input terminal
DI1
Multi-function
input terminal 1
Programmable
multi-function digital
output terminal is referred
to introduction about
output terminal function
of terminal function
parameter (Digital
input/output).
(Common terminal:
COM)
DI2
Multi-function
input terminal 2
DI3
Multi-function
input terminal 3
DI4
Multi-function
input terminal 4
DI5
Multi-function
input terminal 5
DI6
Multi-function
input terminal 6
Qua as pulse signal input
port
Qua as counter pulse
signal input port
Max input frequency:
20KHz
Max input frequency:
500Hz
DI1~DI5
Close
valid
COM
FWD
、
REV